This 1-inch PVC conduit expansion fitting is a telescoping coupling that accommodates thermal expansion and contraction in rigid PVC conduit. It is used in conduit runs where temperature changes cause movement.
1 in. trade size
PVC construction
Telescoping coupling
UL listing
4 in. travel
This 1-inch PVC conduit expansion fitting is a telescoping coupling that accommodates thermal expansion and contraction in rigid PVC conduit. It is used in conduit runs where temperature changes cause movement.
This 1-inch PVC conduit expansion fitting is a telescoping coupling that accommodates thermal expansion and contraction in rigid PVC conduit. It is used in conduit runs where temperature changes cause movement.
1 in. trade size
PVC construction
Telescoping coupling
UL listing
4 in. travel
Technical Specifications
Product information and specifications for the selected item.
SKU: PEJ100
Product Information
Brands we stock
Kraloy
SKU
PEJ100
Category
Conduit Fittings
Technical Details
Fitting Type
Coupling
Conduit Compatibility
PVC, Rigid
Trade Size (in.)
1 in
Material
PVC
Height (in.)
1.59
Width (in.)
1.59
Length (in.)
12.5
Weight (lb.)
0.4784
Construction
Movement mechanism
Two tubes, with one telescoping inside the other
Leakage seal
O-rings to prevent leakage
Telescoping construction
Two tubes, one telescoping inside another
Operating Conditions
Temperature-change trigger
Required when temperature change exceeds 25°F (14°C)
NEC ambient-temperature limit
122 °F
Durability
Corrosion resistance
Resistant to external corrosion and pitting; will not rust
Adjustment
Lubrication
Pre-lubricated for smooth adjusting
Movement
Available travel
4 in
Sealing
Seal type
O-rings
Chemical Resistance
Chemical resistance
Resistant to acids, alkalis and salt solutions
Installation
Required conduit straps
Kraloy nonmetallic straps must be used to secure the conduit
Barrel and conduit support
Clamp the barrel tight; keep conduit loose enough in hangers to allow movement
Piston alignment
The piston must travel straight in the barrel; misalignment can cause binding and prevent proper operation
Mounting orientation
Vertical or horizontal
Support-strap offset
Approximately 1 on either side ft
Vertical orientation
Mount the piston downward in vertical installations to keep dirt from depositing between barrel and piston
Mechanical
Impact and tensile strength
High impact and high tensile strength
Application
Temperature-variation threshold for use
Exceeds 25 °F
Thermal movement function
Designed to compensate for thermal expansion and contraction
PVC conduit thermal-expansion coefficient
3.6 x 10-4 in./ft./°F
Performance
Travel
4 in
Compliance
Listing
UL listed
Applicable standards and listings
CSA C22.2 No. 85; UL Listed; UL514B - UL514C; NEMA TC3