586-554-2000
Mon–Fri 6:30am–5pm · Sat 8am–3pm
586-554-2000
Mon–Fri 6:30am–5pm
Brands we stock: MGM Transformers
This 15 kVA, three-phase dry-type transformer has aluminum windings and converts 480V delta power to 208Y/120V. It is used in three-phase electrical distribution to supply 208V and 120V loads.
This 15 kVA, three-phase dry-type transformer has aluminum windings and converts 480V delta power to 208Y/120V. It is used in three-phase electrical distribution to supply 208V and 120V loads.
This 15 kVA, three-phase dry-type transformer has aluminum windings and converts 480V delta power to 208Y/120V. It is used in three-phase electrical distribution to supply 208V and 120V loads.
Product information and specifications for the selected item.
| Brands we stock | MGM Transformers |
|---|---|
| SKU | T15KVA 480D-120/208Y |
| Category | Electrical Transformers |
| Rated Power (kVA) | 15 |
|---|---|
| Temperature Rise (C) | 150 |
| Winding Material | Aluminum |
| Rated Power (kVA) | 15 |
|---|---|
| Temperature Rise (C) | 150 |
| Factory-default tap setting | Jumpers on taps 3 and 5 for nominal 480 V input |
| Tap adjustment condition | De-energize the primary winding and shut down the transformer before changing taps |
| Secondary terminals and neutral | X1, X2, X3 are output phases; X0 is neutral |
| Maximum utility voltage for connection | Do not connect if utility voltage is above 504 |
| Insulation system rating | 220 °C |
| Secondary output configuration | Four-wire, three-phase output |
| Tap jumper alignment | Use the same tap position on all three coils |
| Frequency | 60 Hz |
| Primary tap-voltage settings | 4-5: 504; 4-6: 492; 3-5: 480; 3-6: 468; 2-6: 456; 3-7: 444; 2-7: 432 V |
| Primary BIL | 10 kV |
| Secondary BIL | 10 kV |
| Primary input terminals | H1, H2, H3 |
| Sound level | Not to exceed 45 dB |
| Adjustment safety | Adjustments by a qualified electrician only; disconnect power before working |
| Winding Material | Aluminum |
|---|---|
| Material | Aluminum |
| Enclosure coating color | ANSI 61 |
| Core design | Low hysteresis and eddy-current losses; flux density kept well below saturation to prevent overheating |
| Core grounding | Core visibly grounded to the enclosure with a flexible grounding conductor |
| Enclosure ventilation | Ventilated |
| Core-and-coil mounting | Bolted to the enclosure base and isolated by rubber vibration-absorbing mounts |
| Application and enclosure rating | Indoor NEMA 1; outdoor NEMA 3R |
| Electrostatic shield | Included |
| Enclosure coating process | Electrostatically deposited polymer-polyester powder coating with a baking cycle |
| Coil construction | Continuous-wound coils impregnated with nonhygroscopic thermosetting varnish |
| Cooling class | AA |
| Certifications and Listings | CSA Certified, cUL Listed, DOE, UL Listed |
|---|
| Height (in.) | 28 |
|---|---|
| Width (in.) | 21 |
| Length (in.) | 14 |
| Weight (lb.) | 235 |
Added to cart