This 225A, 600V AC Class RK5 time-delay fuse has a fiberglass body and interrupts current during overloads. It is used for feeder and branch protection in circuits subject to temporary motor overloads and surge currents.
225A current rating
Fiberglass body
Knife-blade terminals
600V AC rating
300V DC rating
Class RK5 fuse type
This 225A, 600V AC Class RK5 time-delay fuse has a fiberglass body and interrupts current during overloads. It is used for feeder and branch protection in circuits subject to temporary motor overloads and surge currents.
This 225A, 600V AC Class RK5 time-delay fuse has a fiberglass body and interrupts current during overloads. It is used for feeder and branch protection in circuits subject to temporary motor overloads and surge currents.
225A current rating
Fiberglass body
Knife-blade terminals
600V AC rating
300V DC rating
Class RK5 fuse type
Technical Specifications
Product information and specifications for the selected item.
SKU: ECSR225
Product Information
Brands we stock
COOER BUSS
SKU
ECSR225
Category
Fuses, Fuse Blocks & Holders
Key Specs
Current - Maximum
225 A
AC Voltage Rating
600 V AC
DC Voltage Rating
300 V DC
Fits Fuse Class or Type
Class RK5
Electrical Ratings
Current - Maximum
225 A
AC Voltage Rating
600 V AC
DC Voltage Rating
300 V DC
Interrupting rating
200 kA RMS symmetrical
Current-limiting
Yes
Fuse Type & Indication
Fits Fuse Class or Type
Class RK5
Visual Indication
Non-Indicating
Time-delay characteristic
10 seconds (minimum) at 500% rated current
Applicable circuit conditions
Suitable for circuits subject to temporary motor overloads and surge currents
Application
Feeder/branch protection applications
Terminal style
Knife blade
Body type
Knife blade
RoHS status
No
Applicable standards
UL 248-12; CSA C22.2 No. 248.12
CSA standard
CSA C22.2 No. 248.12
Fuse element configuration
Dual-element
UL listed file number
E162363
Minimum time delay at 500% rated current
10 seconds
Element construction
Dual-element
Agency approvals
CE; cULus Listed (file JDDZ.E4273)
Intended application
Feeder/branch protection applications
UL standard
UL 248-12
CSA file number
700489
Protection functions
Motor overload, ground fault, and short-circuit protection