This 250A, 600V AC Class RK5 dual-element time-delay fuse limits fault current and provides overload and short-circuit protection. It is used in circuits subject to temporary motor overloads and surge currents.
250A current rating
600V AC rating
Class RK5 rating
Dual-element time-delay design
Current-limiting protection
This 250A, 600V AC Class RK5 dual-element time-delay fuse limits fault current and provides overload and short-circuit protection. It is used in circuits subject to temporary motor overloads and surge currents.
This 250A, 600V AC Class RK5 dual-element time-delay fuse limits fault current and provides overload and short-circuit protection. It is used in circuits subject to temporary motor overloads and surge currents.
250A current rating
600V AC rating
Class RK5 rating
Dual-element time-delay design
Current-limiting protection
Technical Specifications
Product information and specifications for the selected item.
SKU: ECSR250
Product Information
Brands we stock
COOER BUSS
SKU
ECSR250
Category
Fuses, Fuse Blocks & Holders
Key Specs
Current - Maximum
250 A
AC Voltage Rating
600 V AC
DC Voltage Rating
300 V DC
Fits Fuse Class or Type
Class RK5
Electrical Ratings
Current - Maximum
250 A
AC Voltage Rating
600 V AC
DC Voltage Rating
300 V DC
Current-limiting characteristic
Current limiting
Time-delay
10 seconds minimum at 500% of rated current
Current-limiting protection
Current limitation helps protect downstream components from high fault currents
Selective coordination
2:1 selective coordination amp ratio
DC interrupting rating
20 kAIC at 300 Vdc
Response time at 500%
10 s
AC interrupting rating
200 kAIC at 600 Vac
Motor fuse sizing guidance
As close as 125% of motor FLA
Fuse Type & Indication
Fits Fuse Class or Type
Class RK5
Visual Indication
Non-Indicating
End-cap safety
Reduces exposure to live parts and extends air gap between adjacent mounted fuse blades or housing
Element construction
Dual-element, time-delay design with separate overload and short-circuit elements
Terminal configuration
Blade end x blade end
UL standard
UL 248-12
CE mark
CE marked
cULus listing
Listed, file No. JDDZ.E4273
Protection functions
Motor overload, ground fault and short-circuit protection
Recommended fuse blocks
RM60400-1CR, RM60400-2CR, RM60400-3CR
Overload and surge application
Applicable to circuits subject to temporary motor overloads and surge currents
End-cap construction
Insulated end caps; reduces exposure to live parts and extends air gap
CE marking
CE Marked
Terminal connection
Blade end x blade end
Element configuration
Dual element
CSA standard
CSA C22.2 No. 248.12
Dimensions & Weight
Height (in.)
2.34
Width (in.)
2.34
Length (in.)
11.63
Weight (lb.)
2.45
Product Documents
Bussmann Series Full Line Catalog 1007 — Section 01: Low Voltage Branch Circuit Fuses
Other
Open / download file
Bussmann series FRS-R 600 V Class R 65–600 A Fuse Data Sheet No. 1018
Spec sheet
Open / download file