30 kVA 3-Phase Dry-Type Transformer, 480V Delta to 120/240V Wye

0 Reviews
SKU
T30KVA 480V-120/240

Brands we stock: Jefferson Electric

This 30 kVA, three-phase dry-type transformer has a steel enclosure and converts 480V delta input to 120/240V wye power. It is used in commercial and industrial building power distribution.

  • 30 kVA three-phase rating
  • 480V delta primary
  • 120/240V wye secondary
  • Steel construction
  • Aluminum windings
  • 150°C temperature rise

This 30 kVA, three-phase dry-type transformer has a steel enclosure and converts 480V delta input to 120/240V wye power. It is used in commercial and industrial building power distribution.

Product Overview

This 30 kVA, three-phase dry-type transformer has a steel enclosure and converts 480V delta input to 120/240V wye power. It is used in commercial and industrial building power distribution.

  • 30 kVA three-phase rating
  • 480V delta primary
  • 120/240V wye secondary
  • Steel construction
  • Aluminum windings
  • 150°C temperature rise

Technical Specifications

Product information and specifications for the selected item.

SKU: T30KVA 480V-120/240

Product Information

Brands we stockJefferson Electric
SKUT30KVA 480V-120/240
CategoryElectrical Transformers

Key Specs

Rated Power (kVA)30
Temperature Rise (C)150
Winding MaterialAluminum

Capacity & Ratings

Rated Power (kVA)30
Temperature Rise (C)150
Insulation class220 °C
Center-tap single-phase load limitSingle-phase load on the 120 V center tap must not exceed 5% of the three-phase kVA rating.
Operating frequency60 Hz
Primary tap endpoint settings504 V at tap 1 to 432 V at tap 7, per coil
Primary tap voltage settings504, 492, 480, 468, 456, 444, or 432 V
Primary tap configuration2 taps at 2.5% FCAN and 4 taps at 2.5% FCBN.
Separate-transformer thresholdUse a separate single-phase transformer if the single-phase load exceeds 5%.
120V center-tap loading limitSingle-phase load must not exceed 5% of the three-phase kVA rating; use a separate single-phase transformer above that limit.
Frequency60 standard; 50 optional Hz
Input-side fusingFuse the input side per current NEC requirements.

Construction

Winding MaterialAluminum
MaterialSteel
Tap constructionStaggered front loop taps.
Enclosure finishHeat-cured ASA-61 gray powder coat.
FinishHeat-cured ASA-61 gray powder coat finish
Termination lugsTermination lugs provided on catalog units through 75 kVA.
Three-phase secondary terminalsX1, X2, and X3.
Connection compartmentLarge connection compartment for wiring and installation.
120 V single-phase secondary terminalsX1–X4 or X2–X4.
Installation environmentIndoor and outdoor use.
Secondary terminal connections240V three-phase: X1/X2/X3; 120V single-phase: X1–X4 or X2–X4.
Center-tap locationThe center tap is on the center coil.
High-leg connectionConnect X3 (the high leg) to phase B; do not use X3 for 120 V lighting.
Vibration isolationVibration-isolation pads.
Shield configurationNo shield (model suffix code 0)

Certifications

Certifications and ListingsCSA Certified, cULus Listed, DOE, UL Listed

Dimensions & Weight

Height (in.)25
Width (in.)22
Length (in.)22