Skip to content

350A 600V Class RK5 Time-Delay Fuse

0 Reviews
SKU
ECSR350

Brands we stock: Eaton

This 350 A, 600 V AC Class RK5 time-delay fuse opens a circuit during an overcurrent event. It is used in AC power distribution mains, feeders, and branch circuits.

  • 350 A current rating
  • 600 V AC, 300 V DC voltage ratings
  • Class RK5 fuse class
  • Blade-end terminals
  • Dual-element time-delay operation

This 350 A, 600 V AC Class RK5 time-delay fuse opens a circuit during an overcurrent event. It is used in AC power distribution mains, feeders, and branch circuits.

Product Overview

This 350 A, 600 V AC Class RK5 time-delay fuse opens a circuit during an overcurrent event. It is used in AC power distribution mains, feeders, and branch circuits.

  • 350 A current rating
  • 600 V AC, 300 V DC voltage ratings
  • Class RK5 fuse class
  • Blade-end terminals
  • Dual-element time-delay operation

Technical Specifications

Product information and specifications for the selected item.

SKU: ECSR350

Product Information

Brands we stockEaton
SKUECSR350
CategoryFuses, Fuse Blocks & Holders

Key Specs

Current - Maximum350 A
AC Voltage Rating600 V AC
DC Voltage Rating300 V DC
Fits Fuse Class or TypeClass RK5

Electrical Ratings

Current - Maximum350 A
AC Voltage Rating600 V AC
DC Voltage Rating300 V DC
Short-circuit current limitationGreater current-limitation
Interrupt rating200 kAIC
Motor FLA sizing guidanceAs close as 125% of motor FLA
Transient-load suitabilityApplicable to circuits subject to temporary motor overloads and surge currents
Interrupting rating20 kAIC at 300 Vdc; 200 kAIC at 600 Vac
Response time at 500%10 seconds
Current-limiting characteristicCurrent-limiting
Temporary overload/surge suitabilityFor circuits subject to temporary motor overloads and surge currents

Fuse Type & Indication

Fits Fuse Class or TypeClass RK5
Visual IndicationNon-Indicating
Terminal connectionBlade end x blade end
CE markingCE Marked
Recommended applicationAC power distribution system mains, feeders, and branch circuits
Finger-safe featureFinger safe
Terminal configurationBlade end x blade end
CSA standardCSA C22.2 No. 248.12
Number of elementsDual
Live-part protectionReduces exposure to live parts
Agency listing and standardscULus Listed (file JDDZ.E4273); UL 248-12; CSA C22.2 No. 248.12
Typical applicationsPower panelboards; motor control centers; combination starters; machinery disconnects
End-cap constructionInsulated end caps
Protection functionsMotor overload, ground fault, and short-circuit protection
cULus listingcULus Listed; file No. JDDZ.E4273

Dimensions & Weight

Height (in.)0.81
Width (in.)0.81
Length (in.)5
Weight (lb.)0.4