This 400 A, 600 V AC Class RK5 time-delay fuse interrupts excessive current to help protect electrical circuits. It is used in power-distribution mains, feeders, and branch circuits serving motor, transformer, lighting, or heating loads.
400 A current rating
600 V AC rating
Class RK5 fuse class
300 V DC rating
Time-delay operation
Blade-end connections
This 400 A, 600 V AC Class RK5 time-delay fuse interrupts excessive current to help protect electrical circuits. It is used in power-distribution mains, feeders, and branch circuits serving motor, transformer, lighting, or heating loads.
This 400 A, 600 V AC Class RK5 time-delay fuse interrupts excessive current to help protect electrical circuits. It is used in power-distribution mains, feeders, and branch circuits serving motor, transformer, lighting, or heating loads.
400 A current rating
600 V AC rating
Class RK5 fuse class
300 V DC rating
Time-delay operation
Blade-end connections
Technical Specifications
Product information and specifications for the selected item.
SKU: ECSR400
Product Information
Brands we stock
Eaton
SKU
ECSR400
Category
Fuses, Fuse Blocks & Holders
Key Specs
Current - Maximum
400 A
AC Voltage Rating
600 V AC
DC Voltage Rating
300 V DC
Fits Fuse Class or Type
Class RK5
Electrical Ratings
Current - Maximum
400 A
AC Voltage Rating
600 V AC
DC Voltage Rating
300 V DC
Surge-current behavior
Overrides normal equipment current surges to reduce unnecessary fuse openings
DC interrupting rating
20 kA DC
Current-limiting design
Yes
Recommended applications
AC power-distribution mains, feeders, and branch circuits with inductive (motors, transformers) or non-inductive (lighting, heating) loads
Apparent RMS symmetrical let-through current at 10,000 A prospective SCC (ECSR400 column)
8,550 A
Interrupt rating
200 kAIC
Lower-voltage application
May be applied at voltages below its rating
Apparent RMS symmetrical let-through current at 15,000 A prospective SCC (ECSR400 column)
9,750 A
Motor-backup sizing
125 % FLA
Protection functions
Motor overload, ground fault, and short-circuit protection
Recommended circuit and load types
Mains, feeders and branch circuits with inductive motor or transformer loads
Response time at 500% of rated current
10 s
Fuse Type & Indication
Fits Fuse Class or Type
Class RK5
Visual Indication
Non-Indicating
CE marking
CE Marked
cULus listing
Listed; file No. JDDZ.E4273
Finger-safety feature
Finger safe
CSA certification
Certified HRCI-R per C22.2 No. 248.12; file 700489