Skip to content

60A 3-Pole 600V Heavy-Duty Fusible Safety Switch, NEMA 3R

0 Reviews
SKU
HF362NRA

Brands we stock: Midwest Electric Products, ABB, Siemens

This 60 A, three-pole, 600 V heavy-duty fusible safety switch disconnects electrical equipment and provides fuse-based overcurrent protection. Its NEMA 3R enclosure is intended for outdoor electrical installations.

  • 60 A, 3-pole rating
  • 600 V AC rating
  • Fusible disconnect
  • NEMA 3R enclosure

This 60 A, three-pole, 600 V heavy-duty fusible safety switch disconnects electrical equipment and provides fuse-based overcurrent protection. Its NEMA 3R enclosure is intended for outdoor electrical installations.

Product Overview

This 60 A, three-pole, 600 V heavy-duty fusible safety switch disconnects electrical equipment and provides fuse-based overcurrent protection. Its NEMA 3R enclosure is intended for outdoor electrical installations.

  • 60 A, 3-pole rating
  • 600 V AC rating
  • Fusible disconnect
  • NEMA 3R enclosure

Technical Specifications

Product information and specifications for the selected item.

SKU: HF362NRA

Product Information

Brands we stockMidwest Electric Products, ABB, Siemens
SKUHF362NRA
CategoryDisconnects & Safety Switches

Key Specs

Maximum Amperage (A)60
Phase Type3 Phase
Disconnect TypeSafety Switch
NEMA Enclosure RatingNEMA 3R

Switch Ratings

Maximum Amperage (A)60
Phase Type3 Phase
Horsepower rating, 600 Vac, single-phase, time-delay fuse25.0 hp
Rated frequency50/60 Hz
Horsepower rating, 480 Vac, three-phase, standard fuse15.0 hp
DC horsepower rating at 125 Vdc5.0 hp
Number of wires3 wires
Horsepower rating, 600 Vac, single-phase, standard fuse10.0 hp
Line/load terminal wire range (copper and aluminum)12–2 for both copper and aluminum conductors AWG
Horsepower rating, 480 Vac, single-phase, standard fuse5.0 hp
DC horsepower rating at 250 Vdc10.0 hp
Short-circuit withstand rating, Class H fusing10,000 A rms symmetrical
Horsepower rating, 600 Vac, three-phase, standard fuse15.0 hp
Horsepower rating, 480 Vac, single-phase, time-delay fuse20.0 hp
Horsepower rating, 480 Vac, three-phase, time-delay fuse30.0 hp
Conductor temperature rating60/75 °C
Short-circuit withstand rating, Class R fusing200,000 (unless otherwise noted on the enclosure) A rms symmetrical
Horsepower rating, 600 Vac, three-phase, time-delay fuse50.0 hp

Disconnect Configuration

Disconnect TypeSafety Switch
FusedFused
Knockout pattern F2 knockouts with 1 Ă— 1-1/4 Ă— 1-1/2 Ă— 2 in. KO sizes
Cover interlockFull cover interlocks
Switching mechanismQuick-make, quick-break mechanism
Knockout pattern E3 knockouts with 3/4 Ă— 1 Ă— 1-1/4 Ă— 1-1/2 in. KO sizes
Knockout pattern D2 knockouts with 1/2 Ă— 3/4 Ă— 1 Ă— 1-1/4 in. KO sizes

Enclosure & Certifications

NEMA Enclosure RatingNEMA 3R
Certifications and ListingscULus Listed, UL Listed
Service-equipment suitabilitySuitable when installed in accordance with the National Electrical Code

Dimensions & Weight

Height (in.)22
Width (in.)9.7
Length (in.)7.9
Weight (lb.)18
Mounting holes3 mounting holes, 0.33 in. diameter
Dimensional tolerance±0.125 in