This 60A, 3-pole, 240V non-fused safety switch has a galvanized-steel enclosure and disconnects power to a circuit. It is used outdoors as a local disconnect for electrical equipment.
60A, 3-pole, 240V rating
Galvanized steel enclosure
NEMA 3R enclosure
Non-fused operation
UL Listed
This 60A, 3-pole, 240V non-fused safety switch has a galvanized-steel enclosure and disconnects power to a circuit. It is used outdoors as a local disconnect for electrical equipment.
This 60A, 3-pole, 240V non-fused safety switch has a galvanized-steel enclosure and disconnects power to a circuit. It is used outdoors as a local disconnect for electrical equipment.
60A, 3-pole, 240V rating
Galvanized steel enclosure
NEMA 3R enclosure
Non-fused operation
UL Listed
Technical Specifications
Product information and specifications for the selected item.
SKU: GNF322RA
Product Information
Brands we stock
Siemens
SKU
GNF322RA
Category
Disconnects & Safety Switches
Key Specs
Maximum Amperage (A)
60
Phase Type
3 Phase
Disconnect Type
Safety Switch
NEMA Enclosure Rating
NEMA 3R
Switch Ratings
Maximum Amperage (A)
60
Phase Type
3 Phase
AC short-circuit rating by fuse class
10,000 with Class K/H fuses; 100,000 with Class R fuses AIC
Horsepower ratings
10 HP at 240 V AC, 1-phase; 15 HP at 240 V AC, 3-phase; 10 HP at 250 V DC
Maximum DC circuit voltage
250 V DC
AC short-circuit capacity with fuse protection
10,000 with Class K or H fuse protection; 100,000 with Class R fuse protection AIC
DC short-circuit suitability
Up to 10,000 A RMS symmetrical at 250 V DC, with fuses marked for a 10,000 A, 250 V DC interrupting rating
Disconnect Configuration
Disconnect Type
Safety Switch
Fused
Non-Fused
Mechanical lug tightening torque by wire size
14–10 AWG: 35; 8 AWG: 40; 6 AWG: 45 lb-in
Pole use for DC operation
Outer two poles
Line/load terminal wire ranges
NEC wire-bending range: 14–6 AWG; lug range: 14–2 AWG
Contact design
Double-break, visible-blade design
Switching action
Quick-make and break switching action
Lockout provisions
Padlockable cover latch; multiple OFF-position padlock provisions on handle
Service-equipment use conditions
Suitable as service equipment with a ground-bar kit for 3-phase, 3-wire systems, or a neutral kit for 1-phase, 3-wire or 3-phase, 4-wire systems
Line/load lug tightening torque
35 lb-in for 14–10 AWG; 40 lb-in for 8 AWG; 45 lb-in for 6 AWG