This 800 A, 600 V AC Class L time-delay fuse protects electrical circuits against overcurrent. It is used in electrical distribution and feeder circuits.
800 A current rating
600 V AC rating
Class L fuse
Time-delay operation
Non-indicating design
This 800 A, 600 V AC Class L time-delay fuse protects electrical circuits against overcurrent. It is used in electrical distribution and feeder circuits.
This 800 A, 600 V AC Class L time-delay fuse protects electrical circuits against overcurrent. It is used in electrical distribution and feeder circuits.
800 A current rating
600 V AC rating
Class L fuse
Time-delay operation
Non-indicating design
Technical Specifications
Product information and specifications for the selected item.
SKU: ECSR800
Product Information
Brands we stock
Eaton Bussmann
SKU
ECSR800
Category
Fuses, Fuse Blocks & Holders
Key Specs
Current - Maximum
800 A
AC Voltage Rating
600 V AC
DC Voltage Rating
300 V DC
Electrical Ratings
Current - Maximum
800 A
AC Voltage Rating
600 V AC
DC Voltage Rating
300 V DC
Time-delay response
4 (minimum) at 500% of rated current s
Interrupting rating
300 at 600 Vac; 100 at 300 Vdc kA
Let-through current at 300 kA prospective SCC
31,000 apparent RMS symmetrical at 300,000 prospective SCC
DC interrupting rating
100 kA
AC interrupting rating
300 kA RMS symmetrical
Let-through current at 300,000 A prospective short-circuit current (800 A column; apparent RMS symmetrical)
31,000 A
Selective coordination ratio
2:1 ampacity ratio within the Low-Peak fuse family
Minimum time-delay at 500% of rated current
4 (minimum) s
Fuse Type & Indication
Visual Indication
Non-Indicating
CE marking
CE marked
EU directives
2014/35/EU Low Voltage Directive; 2011/65/EU RoHS Directive
Typical applications
Large distribution switchboards; power panelboards; large machinery disconnects
Fuse-link material
99.9% pure silver links
Protection scope
Overload and short-circuit protection for high-capacity systems, mains and large feeders