Skip to content
ABB

ABB A75 3-Pole Contactor, 125A AC-1, 120VAC Coil, 1 NO + 1 NC Auxiliaries

0 Reviews
SKU
A75-30-11-120V

The ABB A75-30-11-120V is a three-pole lighting contactor rated 125 A AC-1 and 75 A AC-3 at 380/400 V and 55 °C. Its coil is rated 115–120 VAC at 60 Hz or 110 VAC at 50 Hz, and it includes one normally open and one normally closed auxiliary contact.

  • 125 A AC-1 rating
  • 75 A AC-3 current
  • Three-pole main circuit
  • Frequency-specific coil voltage
  • One NO and one NC auxiliary
  • Main-circuit conductor capacity

The ABB A75-30-11-120V is a three-pole lighting contactor rated 125 A AC-1 and 75 A AC-3 at 380/400 V and 55 °C. Its coil is rated 115–120 VAC at 60 Hz or 110 VAC at 50 Hz, and it includes one normally open and one normally closed auxiliary contact.

Product Overview

The ABB A75-30-11-120V is a three-pole lighting contactor rated 125 A AC-1 and 75 A AC-3 at 380/400 V and 55 °C. Its coil is rated 115–120 VAC at 60 Hz or 110 VAC at 50 Hz, and it includes one normally open and one normally closed auxiliary contact.

  • 125 A AC-1 rating
  • 75 A AC-3 current
  • Three-pole main circuit
  • Frequency-specific coil voltage
  • One NO and one NC auxiliary
  • Main-circuit conductor capacity

Technical Specifications

Product information and specifications for the selected item.

SKU: A75-30-11-120V

Product Information

BrandABB
MPNA75-30-11-120V
SKUA75-30-11-120V
CategoryLighting Contactors

Key Specs

Number of Poles3
Coil Voltage115-120 VAC (60 Hz) / 110 VAC (50 Hz)
Contact TypeN.C. and N.O.
Height (in.)4.33

Switching & Electrical

Number of Poles3
Coil Voltage115-120 VAC (60 Hz) / 110 VAC (50 Hz)
Contact TypeN.C. and N.O.
AC-3 rated operational power37 kW at 380/400 V; 40 kW at 690 V; 45 kW at 500 V
AC-15 auxiliary-circuit current ratings6 A at 24/127 V; 4 A at 220/240 V; 3 A at 380/400 V; 2 A at 500/690 V
Ambient temperature limitsOperating: −25 to +55 °C with thermal overload relay; −40 to +55 °C without relay at 0.85–1.1 Uc; −40 to +70 °C without relay at Uc. Storage: −60 to +80 °C
Main-circuit conductor capacityRigid: 6–25 mm²; flexible with cable end: 6–16 mm²
Auxiliary-circuit conductor capacityRigid: 1–4 mm²; flexible with cable end: 0.75–2.5 mm²
Maximum permissible operating altitude3000 m
AC-3 rated making and breaking capacityBreaking: 8 × Ie; making: 10 × Ie (IEC 60947-4-1)
ConstructionBlock-type design; AC-operated control circuit with laminated magnet circuit
Maximum electrical switching frequencyAC-1/AC-3: 600 cycles per hour; AC-2/AC-4: 150 cycles per hour cycles/hour
Coil average pull-in apparent power190 VA at 50 Hz; 180 VA at 60 Hz
Auxiliary-circuit conventional free-air thermal current16 A at 40 °C (IEC 60947-5-1)
Degree of protectionIP40 (auxiliary terminals)
Rated impulse withstand voltage8 kV
Maximum breaking capacity1300 A at 440 V; 630 A at 690 V; cos φ=0.45 (0.35 for Ie > 100 A)
AC-1 current derating at 690 V105 A at 55 °C; 85 A at 70 °C
Standards, EMC and RoHSIEC 947-1/947-4-1 and EN 60 947-1/60 947-4-1; EMC per amendment A11 to IEC 947-1 and EN 60 947-1, and amendment 2 to IEC 947-4-1; RoHS per EU Directive 2011/65/EU
Main terminal tightening torque and driverM6 terminals: 4 N·m; Pozidriv No. 2
Auxiliary-circuit short-circuit fuse10 A gG
AC-6b capacitor-switching power at 690 V82 kvar at 40/55 °C; 70 kvar at 70 °C (50/60 Hz)
Mechanical durability10 million cycles
AC-3 rated operational currentAt 55 °C: 75 A at 380/400 V; 46 A at 690 V; 28 A at 1000 V
Intended applicationsFor 3-phase motor control; also suitable for isolation, capacitor switching and lighting
Rated operational and insulation voltagesMain-circuit Ue: 1000 V; Ui: 1000 V (IEC 60947-4-1/VDE 0110 Gr. C), 690 V (IEC 60947-5-1/VDE 0110 Gr. C), 600 V (UL/CSA)

Dimensions & Weight

Height (in.)4.33
Width (in.)3.23
Length (in.)4.25
Weight (lb.)2.65
DIN-rail mounting profilesEN/IEC 60715 35 × 15 mm and 75 mm mounting profiles are shown

Product Documents

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.