Skip to content
ABB

ABB ReliaMod 800A 1-Phase Main Breaker Module, 120/240VAC, 65kAIC@240V

0 Reviews
SKU
RMM1BL8R

The ABB RMM1BL8R is a ReliaMod 800 A main breaker module for 1-phase, 3-wire 120/240 VAC systems, rated 65 kAIC at 240 V. It uses an XT6N frame and TMA trip unit in an N3R outdoor enclosure, with factory-installed mechanical lugs and top- or bottom-feed capability.

  • 800 A Main Breaker Rating
  • 120/240 VAC, 1-Phase, 3-Wire
  • 65 kAIC at 240 V
  • N3R Outdoor Enclosure
  • Phase, Neutral and Ground Lugs
  • UL Listed

Product Overview

The ABB RMM1BL8R is a ReliaMod 800 A main breaker module for 1-phase, 3-wire 120/240 VAC systems, rated 65 kAIC at 240 V. It uses an XT6N frame and TMA trip unit in an N3R outdoor enclosure, with factory-installed mechanical lugs and top- or bottom-feed capability.

Technical Specifications

Product information and specifications for the selected item.

SKU: RMM1BL8R

Product Information

BrandABB
MPNRMM1BL8R
SKURMM1BL8R
UPC / GTIN783164672510
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)800
Voltage120/240 V AC
Interruption TypeStandard Trip
Breaker TypeMain Breaker
Neutral Connection TypeNeutral

Electrical Ratings

Maximum Amperage (A)800
Voltage120/240 V AC
Interruption TypeStandard Trip
Phase and neutral lug conductor rangeFactory-installed mechanical lugs; (3) 2/0 AWG–400 kcmil Cu/Al AWG/kcmil
Ground lug conductor range(2) #6 AWG–350 kcmil Cu/Al AWG/kcmil
Phase and wire configuration1-phase, 3-wire
Main ground lugs(2) #6–350 Al/Cu AWG/kcmil
Lugs per phase and neutral(3) 2/0–400 Al/Cu AWG/kcmil

Breaker Configuration

Breaker TypeMain Breaker
Neutral Connection TypeNeutral
Series TypeReliaMod
Bottom end-wall constructionRemovable blank end wall; no knockout
Breaker access and lockingBreaker access door with padlock provision
Feed locationBottom/Top
Circuit breaker trip unitTMA
Circuit breaker frameXT6N
Grounding and bonding positionsBonding-jumper position and alternate ground position identified
Incoming feed orientationBottom or top
Horizontal bus compatibilityNot directly compatible with GE Meter Mod III; requires a bus transition adapter section.
Phase-lug barriersLine-side barriers over phase lugs

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingsUL Listed
Enclosure rating and environmentN3R outdoor
Enclosure ratingN3R Outdoor

Dimensions & Weight

Height (in.)52.37
Weight (lb.)160

Product Documents

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.