Skip to content
ABB

ABB S201-K15 1P 15A K-Characteristic Miniature Circuit Breaker

0 Reviews
SKU
S201-K15

ABB's S201-K15 is a single-pole S200 miniature circuit breaker rated 15 A, with a K-characteristic trip and a 230/400 V AC rating. It is specified for DIN-rail mounting and uses delayed thermal overload and electromechanical short-circuit trip mechanisms.

  • 15 A Rated Current
  • Single-Pole Configuration
  • K-Characteristic Trip
  • 230/400 V AC Rating
  • 10 kA Ultimate Breaking Capacity
  • DIN-Rail Mounting

ABB's S201-K15 is a single-pole S200 miniature circuit breaker rated 15 A, with a K-characteristic trip and a 230/400 V AC rating. It is specified for DIN-rail mounting and uses delayed thermal overload and electromechanical short-circuit trip mechanisms.

Product Overview

ABB's S201-K15 is a single-pole S200 miniature circuit breaker rated 15 A, with a K-characteristic trip and a 230/400 V AC rating. It is specified for DIN-rail mounting and uses delayed thermal overload and electromechanical short-circuit trip mechanisms.

  • 15 A Rated Current
  • Single-Pole Configuration
  • K-Characteristic Trip
  • 230/400 V AC Rating
  • 10 kA Ultimate Breaking Capacity
  • DIN-Rail Mounting

Technical Specifications

Product information and specifications for the selected item.

SKU: S201-K15

Product Information

BrandABB
MPNS201-K15
SKUS201-K15
UPC / GTIN4016779645133
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)15
Voltage230/400 V AC
Interruption TypeStandard Trip
Breaker TypeMiniature
Mounting TypeDin Rail
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)15
Voltage230/400 V AC
Interruption TypeStandard Trip
Ambient Air TemperatureOperation: -25 to +55; storage: -40 to +70 °C
Electrical and mechanical enduranceElectrical: 20,000 AC cycles; mechanical: 20,000 cycles
Power loss per pole at rated operating conditions1.733 W
Ambient temperature limitsOperation: -25 to +55; storage: -40 to +70 °C
Pollution degree3
Overvoltage categoryIII
Shock resistance25 g; 2 shocks; 13 ms
Rated conditional short-circuit current (Inc)230 V: 10; 400 V: 10 kA
Rated frequency50 / 60 Hz
Rated service short-circuit breaking capacity (Ics)133 V AC: 15; 230 V AC: 7.5 kA
UL 1077 interrupting rating277 V AC: 6; 60 V DC: 10; 120 V: 10 kA
Degree of protectionIP20; IP40; enclosure with cover: IP40
Rated ultimate short-circuit breaking capacity (Icu)133 V AC: 20; 230 V AC: 10; 24 V DC: 20; 60 V DC: 10; 230 V: 10; 400 V: 10 kA
Vibration resistance20 cycles with load 0.8 In; 5 g, 5 to 150 to 5 Hz
Current-limiting designCurrent limiting
Energy limiting class3

Breaker Configuration

Breaker TypeMiniature
Mounting TypeDin Rail
Neutral Connection TypeNon-Neutral
Series TypeS200
Power supply connectionArbitrary
Connecting capacityBusbar: 10 / 10; flexible with ferrule or flexible: 0.75 to 25; rigid or stranded: 0.75 to 35 mm²
Terminal tightening torque2.8 N·m
Overcurrent trip mechanismsDelayed thermal trip for overload protection; electromechanic trip for short-circuit protection
Actuator and housing material/finishActuator: Insulation Group II, black, sealable; housing: Insulation Group II, RAL 7035
Wire stripping length12.5 mm
Permitted mounting positionAny
Screw terminal constructionFailsafe Bi-directional Cylinder-lift Terminal

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsPro Pack

Certifications

Certifications and ListingsCSA Certified, ROHS, UL Recognized

Dimensions & Weight

Height (in.)3.4646
Width (in.)0.689
Length (in.)2.7165
Weight (lb.)0.2756

Product Documents