The Mersen AJT30 is a 30 A Class J time-delay fuse rated 600 V AC and 400 V DC. Its time-delay characteristics handle typical motor and transformer inrush currents, while its current-limiting design is specified for low peak let-through current.
30 A maximum current
Class J time-delay operation
600 V AC / 400 V DC ratings
Current-limiting design
0.814 Ă— 0.814 Ă— 2.25 in dimensions
Non-indicating fuse
The Mersen AJT30 is a 30 A Class J time-delay fuse rated 600 V AC and 400 V DC. Its time-delay characteristics handle typical motor and transformer inrush currents, while its current-limiting design is specified for low peak let-through current.
The Mersen AJT30 is a 30 A Class J time-delay fuse rated 600 V AC and 400 V DC. Its time-delay characteristics handle typical motor and transformer inrush currents, while its current-limiting design is specified for low peak let-through current.
30 A maximum current
Class J time-delay operation
600 V AC / 400 V DC ratings
Current-limiting design
0.814 Ă— 0.814 Ă— 2.25 in dimensions
Non-indicating fuse
Technical Specifications
Product information and specifications for the selected item.
SKU: AJT30
Product Information
Brand
Mersen
MPN
AJT30
SKU
AJT30
Category
Fuses, Fuse Blocks & Holders
Key Specs
Current - Maximum
30 A
AC Voltage Rating
600 V AC
DC Voltage Rating
400 V DC
Fits Fuse Class or Type
Class J
Electrical Ratings
Current - Maximum
30 A
AC Voltage Rating
600 V AC
DC Voltage Rating
400 V DC
Interrupting rating
200 AC; 100 DC kA
Self-certified interrupting rating
300 kA
Selectivity ratio
2-to-1
Frequency
50/60 Hz
Peak let-through behavior
Current-limiting design for low peak let-through current
Fuse Type & Indication
Fits Fuse Class or Type
Class J
Visual Indication
Non-Indicating
Current-limiting characteristic
Current-limiting design
Inrush-current handling
Time-delay characteristics handle typical motor and transformer inrush currents
Filler material
High-grade silica
Body material
Fiberglass body
UL listing
UL listed to standard 248-8, File E2137
Arc-quenching filler
High-grade silica filler
Applicable standard
IEC 60269-2-1
DC listing
DC listed to UL standard 248
No-damage protection
IEC Type 2 No Damage protection for main, feeder, and branch circuits
CSA certification
CSA standard C22.2 No. 248.8
Terminal type
Ferrule
Operating characteristic
Time delay for motor starting and transformer inrush
Listings and standards
UL 248-8 (File E2137); DC listed to UL 248; CSA C22.2 No. 248.8; IEC 60269-2-1
Dimensions & Weight
Height (in.)
0.814
Width (in.)
0.814
Length (in.)
2.25
Weight (lb.)
0.097
Product Documents
Time Delay Class J Fuse — Peak Let-Through Current Data, AJT(8–60)ID / AJT(5–60)
Other
Open / download file
Time Delay Class J Fuse — Average Melting Time Current Curve, 15–30 Amps
Other
Open / download file