Amp-Trap 2000 AJT60 Class J Time-Delay Fuse, 60A, 600VAC
0 Reviews
SKU
AJT60
The Mersen AJT60 is a 60 A Class J time-delay fuse with ferrule terminals, non-indicating operation, and a listed 400 VDC rating. Product sources show both 600 VAC and 700 VAC, so verify the AC rating before selection.
60 A Class J Time-Delay
600 VAC / 400 VDC Ratings
AC/DC Interrupting Ratings
Ferrule Terminals
Low Peak Let-Through Current
Non-Indicating Operation
The Mersen AJT60 is a 60 A Class J time-delay fuse with ferrule terminals, non-indicating operation, and a listed 400 VDC rating. Product sources show both 600 VAC and 700 VAC, so verify the AC rating before selection.
The Mersen AJT60 is a 60 A Class J time-delay fuse with ferrule terminals, non-indicating operation, and a listed 400 VDC rating. Product sources show both 600 VAC and 700 VAC, so verify the AC rating before selection.
60 A Class J Time-Delay
600 VAC / 400 VDC Ratings
AC/DC Interrupting Ratings
Ferrule Terminals
Low Peak Let-Through Current
Non-Indicating Operation
Technical Specifications
Product information and specifications for the selected item.
SKU: AJT60
Product Information
Brand
Mersen
MPN
AJT60
SKU
AJT60
UPC / GTIN
782001962388
Category
Fuses, Fuse Blocks & Holders
Key Specs
Current - Maximum
60 A
AC Voltage Rating
700 V AC
DC Voltage Rating
400 V DC
Fits Fuse Class or Type
Class J
Electrical Ratings
Current - Maximum
60 A
AC Voltage Rating
700 V AC
DC Voltage Rating
400 V DC
Interrupting rating
200 kA AC; 100 kA DC; self-certified 300 kA interrupting rating (UL-witnessed tests).
Selectivity
2-to-1 selectivity to help prevent nuisance shutdowns.
IEC Type 2 No Damage protection for main, feeder, and branch circuits.
EU declaration
The declaration covers Low Voltage Directive 2014/35/EU and RoHS Directive 2011/65/EU as amended by (EU) 2015/863, and IEC 60269-1 Ed.4.2:2014 and IEC 60269-2 Ed.4.0:2010. AJT60 is listed with Exemption 6(c).
Hazardous-location installation
Suitable for NEC Class I Division 2 hazardous locations; Mersen highly recommends installation in a certified sealed enclosure for that location.
Identification and traceability
Date and catalog number are metal-embossed for traceability and lasting identification.
UL listing
Listed to UL standard 248-8
UK declaration
The UK declaration covers the Electrical Equipment (Safety) Regulations 2016 and UK hazardous-substances regulations 2012, plus EN 60269-1:2007/A1:2009/A2:2014 and HD 60269-2:2013. AJT60 is listed with Exemption 6(c).
DC listing
DC listed to UL standard 248
Protection type and application
IEC Type 2 no-damage protection for main, feeder, and branch circuits
Applications
Listed applications include motor circuits, mains, feeders, branch circuits, lighting, heating, general loads, transformers, control panels, circuit-breaker back-up, bus duct, and load centers.
Listings and standards
UL listed to standard 248-8 (File E2137); DC listed to UL 248; CSA certified to C22.2 No. 248.8; IEC 60269-2-1.
CSA certification
CSA certified to C22.2 No. 248.8
Terminal style
Ferrule
IEC standard
60269-2-1
Inrush-current handling
Time delay for motor starting and handling typical motor and transformer inrush currents.
Dimensions & Weight
Height (in.)
1.062
Width (in.)
1.062
Length (in.)
2.37
Weight (lb.)
0.167
Body construction
Fiberglass body; dimensional stability in harsh industrial settings
Body material
Fiberglass body provides dimensional stability in harsh environments.
Filler material
High-grade silica filler supports fast arc quenching.
Product Documents
Peak Let-Through Current Data — AJT (5–60) and AJT (8–60)ID, 15–60 A, 600 V (25360)
Other
Open / download file
Melting Time–Current Curve — AJT 35–60 A, 600 V (24362)
Other
Open / download file
Outline Dimensions — AJT (35–60)(ID), Class J Time Delay (17928)
Drawing photometric
Open / download file
UK Declaration of Conformity — Cylindrical Fuse Links (UKCA, No. 22-0004)
Certification compliance
Open / download file
Declaration of Conformity — UL Class Type J Fuse Links (CE/RoHS, No. 20-0004)
Certification compliance