J03AUSA30600CGXM,11BE,44G

The ASCO Series 300 J-frame automatic transfer switch is rated 600 A, three-pole, for 120/208 V three-phase systems. It provides open-transition operation and is service-entrance rated, with a utility-side service-equipment breaker and a Type 3R secure enclosure.

  • 600 A, Three-Pole Rating
  • 120/208 V Three-Phase System
  • Automatic Open-Transition Transfer
  • Service-Entrance Rated
  • Type 3R Secure Enclosure
  • UL Listed

Product Overview

The ASCO Series 300 J-frame automatic transfer switch is rated 600 A, three-pole, for 120/208 V three-phase systems. It provides open-transition operation and is service-entrance rated, with a utility-side service-equipment breaker and a Type 3R secure enclosure.

Technical Specifications

Product information and specifications for the selected item.

SKU: J03AUSA30600CGXM,11BE,44G

Product Information

BrandASCO
MPNJ03AUSA30600CGXM,11BE,44G
SKUJ03AUSA30600CGXM,11BE,44G
CategoryAutomatic Transfer Switches

Key Specs

Maximum Amperage (A)600
Automatic/ManualAutomatic
Certifications and ListingsUL Listed

Electrical Ratings

Maximum Amperage (A)600
Ground rating20% rated
Service-entrance breaker trip characteristics80%-rated; electronic trip unit with long and instantaneous trip settings
Transfer-switch short-circuit rating42 kA RMS symmetrical at 480 V when protected by a circuit breaker with maximum 0.05 s response.
Emergency-source short-circuit rating65 at 240 V; 42 at 480 V kA RMS symmetrical
Power-lug conductor compatibilityCopper or aluminum (Cu/Al) cable
Normal-source conductor size range3/0–500 MCM
Service-disconnect breakerSquare D, 80%-rated Type LLL molded-case circuit breaker.
Normal-source short-circuit rating125 at 240 V; 100 at 480 V kA RMS symmetrical
Neutral rating100% rated
Specified frequency60 Hz
Neutral configurationSolid neutral
Load and emergency-source lug conductor rangeTwo 3/0–600 MCM conductors per phase and neutral for both load and emergency source. AWG/MCM
Breaker trip settingsElectronic trip unit with long- and instantaneous-trip settings.
Ground lug conductor rangeSix 1/0–600 MCM ground conductors. AWG/MCM
Power and control wire requirementsPower cables: Cu/Al wire rated at least 90°C, sized by 75°C ampacity. Controls: Cu wire rated at least 60°C.
Normal-source lug conductor rangeTwo 3/0–500 MCM conductors per phase and neutral; mechanical screw-type lugs for copper/aluminum cable. AWG/MCM

Transfer & Features

Automatic/ManualAutomatic
FeaturesMountable, On/Off Switch, Overload Protection, Water Resistant
Enclosure material and finishCode-gauge steel with an ANSI 61 gray polyester semi-gloss electrostatic-powder finish.
MountingFloor-mounted enclosure.
Section arrangementSeparate service-equipment and transfer-switch sections; the service section contains the disconnect breaker and grounding/bonding provisions.
Door hardwareExterior doors have padlockable handles with a 3-point latch.
Service-entrance section layoutSeparate service-equipment and transfer-switch sections
Cable entryCable entry is supported from the top or bottom for services and load.
Access orientationFront access only.

Certifications

Certifications and ListingsUL Listed

Dimensions & Weight

Recommended service clearanceFront: 38; rear: none. in

Product Documents

  • ASCO Series 300SE JAUS 600 A Type 3R/3RX — Outline and Mounting Drawing 805717-005 Drawing photometric Open / download file
  • Limited Warranty — Series 150, 200, 300 and 4000 Power Transfer Switches (381339-334) Warranty Open / download file
  • ASCO Series 300 Service Entrance Power Transfer Switch Data Sheet (Publication 2007 R5) Spec sheet Open / download file