The Eaton Bussmann Low-Peak LP-CC-30 is a 30 A Class CC, dual-element time-delay, current-limiting fuse rated 600 V AC and 300 V DC. Its interrupting ratings are 200 kAIC at 600 V AC and 20 kAIC at 300 V DC.

  • 30 A Current Rating
  • 600 VAC / 300 VDC Ratings
  • Class CC Fuse
  • Dual-Element Time Delay
  • Interrupting Ratings
  • Rejection-Style Fuse

Product Overview

The Eaton Bussmann Low-Peak LP-CC-30 is a 30 A Class CC, dual-element time-delay, current-limiting fuse rated 600 V AC and 300 V DC. Its interrupting ratings are 200 kAIC at 600 V AC and 20 kAIC at 300 V DC.

Technical Specifications

Product information and specifications for the selected item.

SKU: LP-CC-30

Product Information

BrandEaton Bussmann series
MPNLP-CC-30
SKULP-CC-30
UPC / GTIN051712180313
CategoryFuses, Fuse Blocks & Holders

Key Specs

Current - Maximum30 A
AC Voltage Rating600 V AC
DC Voltage Rating300 V DC
Fits Fuse Class or TypeClass CC

Electrical Ratings

Current - Maximum30 A
AC Voltage Rating600 V AC
DC Voltage Rating300 V DC
Rated operating frequency45–62 Hz
Interrupting rating200 kAIC at 600 Vac; 20 kAIC at 300 Vdc
Response time at 200%12 s
Time-delay response12 seconds minimum at 200% of rated current
Selective coordination ratio2:1 within the Low-Peak fuse family

Fuse Type & Indication

Fits Fuse Class or TypeClass CC
Visual IndicationNon-Indicating
Conformity and environmental marksCE Marked; RoHS Compliant
Motor controller protectionProper sizing can provide Type 2 “No Damage” coordinated protection for NEMA and IEC motor controllers
Recommended compatible blocks and holdersBCM603-x_ modular blocks; CHCCxD_ DIN-rail holders; CCP2-30CC; HPS-RR; HEZ
Other complianceCE marked; RoHS compliant
ShapeCylindrical
End connectionFerrule end x ferrule end
CSA certificationCSA Certified, Class 1422-02; File 53787
Rejection feature behaviorPrevents insertion of lesser-rated supplementary fuses when used with an appropriate fuse block
Tube materialMelamine tube
Fuse rejection behaviorWith an appropriate fuse block, prevents insertion of incorrect supplementary fuses
UL listingUL Listed to Std. 248-4; Guide JDDZ; File E4273
Element constructionDual-element
Element configurationDual
Safety certificationsUL Listed; CSA Certified
ApplicationSpecialized circuits and industrial control
Motor and relay circuit suitabilityTime-delay behavior supports close sizing on small motor and relay circuits

Dimensions & Weight

Height (in.)0.41
Width (in.)0.41
Length (in.)1.5
Weight (lb.)0.015