The Eaton CH270 is a 70 A, two-pole standard-trip circuit breaker rated 120/240 V AC, with a 10 kAIC interrupt rating and common-trip operation. It uses plug-on mounting for Type CH loadcenters and is UL Listed and CSA Certified.
The Eaton CH270 is a 70 A, two-pole standard-trip circuit breaker rated 120/240 V AC, with a 10 kAIC interrupt rating and common-trip operation. It uses plug-on mounting for Type CH loadcenters and is UL Listed and CSA Certified.
The Eaton CH270 is a 70 A, two-pole standard-trip circuit breaker rated 120/240 V AC, with a 10 kAIC interrupt rating and common-trip operation. It uses plug-on mounting for Type CH loadcenters and is UL Listed and CSA Certified.
Product information and specifications for the selected item.
| Brand | Eaton |
|---|---|
| MPN | CH270 |
| SKU | CH270 |
| UPC / GTIN | 782113101897 |
| Category | Circuit Breakers |
| Maximum Amperage (A) | 70 |
|---|---|
| Voltage | 120/240 V AC |
| Interruption Type | Standard Trip |
| Breaker Type | Standard |
| Mounting Type | Plug-On |
| Neutral Connection Type | Neutral |
| Maximum Amperage (A) | 70 |
|---|---|
| Voltage | 120/240 V AC |
| Interruption Type | Standard Trip |
| Trip curve response | Avoids nuisance tripping on mild overloads and reacts almost instantaneously to severe short-circuit conditions |
| Wire size range | #14-2 AWG Cu/Al |
| Compatible Cu/Al conductor temperature | 60 or 75 °C |
| Conductor temperature class | 60 or 75 °C |
| Conductor size range | #14-2 Cu/Al AWG |
| Interrupt rating | 10 kAIC |
| Trip characteristic | Inverse time element tripping operation |
| Breaker Type | Standard |
|---|---|
| Mounting Type | Plug-On |
| Neutral Connection Type | Neutral |
| Series Type | CH |
| Loadcenter restriction | Not for use in Type BR loadcentres |
| Handle markings | ON-OFF indication and breaker ampere rating |
| Required panel spaces | Two 3/4-inch spaces |
| Handle design | Trip-free handle design |
| Switch mechanism | Quick-make, quick-break switch mechanism |
| Trip action | Common trip; all poles operate simultaneously |
| Compatible loadcenters | Type CH Loadcenters |
| Trip arrangement | Common breaker trip |
| Tripped handle position | Trips to the OFF position |
| Bundle/Single | Single Product |
|---|---|
| Pack Options | Single Item |
| Certifications and Listings | CSA Certified, UL Listed |
|---|---|
| HACR equipment application | Marked for heating, air conditioning and refrigeration (HACR) equipment application |
| Height (in.) | 2.6 |
|---|---|
| Width (in.) | 3.2 |
| Length (in.) | 1.5 |
| Weight (lb.) | 0.65 |
Added to cart