Skip to content

Eaton Fusetron 175A Class RK5 Dual-Element Fuse

0 Reviews
SKU
ECSR175

The Eaton ECSR175 is a 175 A, 600 V Fusetron dual-element Class RK5 fuse with current-limiting operation. It is specified for feeder/branch protection and listed load types include inductive motor and transformer loads and non-inductive lighting and heating loads.

  • 175 A, 600 V rating
  • Class RK5 fuse
  • Dual-element construction
  • Current-limiting operation
  • AC and DC interrupt ratings
  • Blade-end terminals

Product Overview

The Eaton ECSR175 is a 175 A, 600 V Fusetron dual-element Class RK5 fuse with current-limiting operation. It is specified for feeder/branch protection and listed load types include inductive motor and transformer loads and non-inductive lighting and heating loads.

Technical Specifications

Product information and specifications for the selected item.

SKU: ECSR175

Product Information

BrandEaton
SKUECSR175
CategoryFuses, Fuse Blocks & Holders

Key Specs

Current - Maximum175 A
AC Voltage Rating600 V AC
DC Voltage Rating300 V DC
Fits Fuse Class or TypeClass RK5

Electrical Ratings

Current - Maximum175 A
AC Voltage Rating600 V AC
DC Voltage Rating300 V DC
DC interrupting rating20,000 A DC
Response time at 500% of rating10 seconds
Motor backup sizing guidance125% FLA for motor backup protection
Interrupt rating200 kAIC
Motor-backup sizing basis125 % FLA
AC interrupting rating200 kAIC

Fuse Type & Indication

Fits Fuse Class or TypeClass RK5
Visual IndicationNon-Indicating
Current-limiting operationYes
Surge handlingOverrides normal equipment current surges to reduce unnecessary fuse openings
UL listingUL Listed (file E162363)
Terminal connectionBlade end x blade end
Recommended applicationFeeder/branch protection applications
Fuse operating characteristicCurrent-limiting
Terminal styleBlade end x blade end
CSA standardCSA C22.2 No. 248.12
Agency approvals and standardsCE marked; cULus listed (file JDDZ.E4273); UL 248-12; CSA C22.2 No. 248.12
RoHS statusNo
Protection functionsMotor overload, ground-fault, and short-circuit protection
Supported load typesInductive motor/transformer loads and non-inductive lighting/heating loads

Dimensions & Weight

Height (in.)0.81
Width (in.)0.81
Length (in.)5
Weight (lb.)0.4