Skip to content

Eaton Series C GHB 30A 3P Molded-Case Circuit Breaker

0 Reviews
SKU
GHB3030

Eaton’s Series C GHB3030 is a 30 A, three-pole molded-case circuit breaker with a fixed thermal-magnetic trip and bolt-on mounting. It is rated 480Y/277 V AC and 125/250 V DC, is UL Listed and HACR rated, and has interrupting ratings of 65 kAIC at 240 V AC and 14 kAIC at 480Y/277 V AC.

  • 30 A, Three-Pole Rating
  • AC and DC Voltage Ratings
  • 65/14 kAIC Interrupting Ratings
  • Fixed Thermal-Magnetic Common Trip
  • Bolt-On Mounting
  • 10–1/0 AWG Cu/Al Terminals

Product Overview

Eaton’s Series C GHB3030 is a 30 A, three-pole molded-case circuit breaker with a fixed thermal-magnetic trip and bolt-on mounting. It is rated 480Y/277 V AC and 125/250 V DC, is UL Listed and HACR rated, and has interrupting ratings of 65 kAIC at 240 V AC and 14 kAIC at 480Y/277 V AC.

Technical Specifications

Product information and specifications for the selected item.

SKU: GHB3030

Product Information

BrandEaton
MPNGHB3030
SKUGHB3030
UPC / GTIN786679911273
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)30
Voltage480Y/277 V AC
Interruption TypeStandard Trip
Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral

Electrical Ratings

Maximum Amperage (A)30
Voltage480Y/277 V AC
Interruption TypeStandard Trip
Interrupting rating65 at 240 Vac; 14 at 480Y/277 Vac kAIC
480 V system compatibilityNot suitable for 480 V three-phase delta systems
Frequency rating50/60 Hz
Time-current curve reference conditionsThe time-current curve reference is based on 40°C ambient and a cold start; connected with four feet of rated wire (60/75°C) per terminal and tested in open air with current in all poles.
480 V three-phase delta suitabilityNot suitable for 480 V three-phase delta systems.

Breaker Configuration

Breaker TypeStandard
Mounting TypeBolt-On
Neutral Connection TypeNon-Neutral
Series TypeSeries C
Standard terminal constructionPressure-type terminal with aluminum body; slotted screw head
DC pole configurationUse the two outside poles for DC application
Pole trip operationCommon trip
Reverse-feed suitabilitySuitable for reverse-feed use
Trip-unit interchangeabilityNon-interchangeable
Frame sizeG-frame
Standard terminal wire range10–1/0 AWG
Supported conductor materialCopper or aluminum (Cu/Al)

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingsUL Listed
HACR ratingHACR rated

Dimensions & Weight

Height (in.)4
Width (in.)3
Length (in.)2.63
Weight (lb.)1.75

Product Documents

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.