The Eaton BR280 is a Type BR, 80 A, two-pole plug-on circuit breaker rated 120/240 V AC. It has common-trip thermal-magnetic operation and a 10 kAIC interrupting capacity at 120/240 V AC, and is specified for Type BR loadcenters.
80 A Current Rating
120/240 V AC Rating
Two-Pole Common Trip
10 kAIC Interrupting Capacity
Type BR Loadcenter Compatibility
Plug-On Mounting
The Eaton BR280 is a Type BR, 80 A, two-pole plug-on circuit breaker rated 120/240 V AC. It has common-trip thermal-magnetic operation and a 10 kAIC interrupting capacity at 120/240 V AC, and is specified for Type BR loadcenters.
The Eaton BR280 is a Type BR, 80 A, two-pole plug-on circuit breaker rated 120/240 V AC. It has common-trip thermal-magnetic operation and a 10 kAIC interrupting capacity at 120/240 V AC, and is specified for Type BR loadcenters.
80 A Current Rating
120/240 V AC Rating
Two-Pole Common Trip
10 kAIC Interrupting Capacity
Type BR Loadcenter Compatibility
Plug-On Mounting
Technical Specifications
Product information and specifications for the selected item.
SKU: BR280
Product Information
Brand
Eaton
MPN
BR280
SKU
BR280
UPC / GTIN
786676363174
Category
Circuit Breakers
Key Specs
Maximum Amperage (A)
80
Voltage
120/240 V AC
Interruption Type
Standard Trip
Breaker Type
Standard
Mounting Type
Plug-On
Neutral Connection Type
Non-Neutral
Electrical Ratings
Maximum Amperage (A)
80
Voltage
120/240 V AC
Interruption Type
Standard Trip
Conductor size range
#8-1/0 AWG Cu/Al
Thermal calibration
Uncompensated; calibrated to meet Option B requirements at 40 °C
Wire size range
#8–1/0 Cu/Al AWG
Instantaneous trip range
850–1700 A
Conductor temperature class
Cu/Al conductors rated 60 °C or 75 °C
Breaker Configuration
Breaker Type
Standard
Mounting Type
Plug-On
Neutral Connection Type
Non-Neutral
Series Type
Type BR
Installation orientation
Suitable for reversed line/load connections and inverted mounting
Handle behavior on trip
Trip-free; handle assumes a mid-position between ON and OFF after automatic tripping
Compatible loadcenters
Type BR Loadcenters
Trip type
Common breaker trip
Trip arrangement
Common breaker trip
Pack & Smart Features
Bundle/Single
Single Product
Pack Options
Single Item
Certifications
Certifications and Listings
UL Listed
Dimensions & Weight
Height (in.)
2.5
Width (in.)
2.9
Length (in.)
1.9
Weight (lb.)
0.6
Product Documents
Trip Curves TC003002EN — Type BR thermal magnetic trip curve results
Other
Open / download file