The Generac RTSN400J3 is a 400 A automatic transfer switch for 120/240 V three-phase systems, with open-transition operation. Its non-service-entrance, non-fused design has a 3-pole mechanism with an unswitched neutral and a NEMA 3R steel enclosure specified for indoor or outdoor use.
The Generac RTSN400J3 is a 400 A automatic transfer switch for 120/240 V three-phase systems, with open-transition operation. Its non-service-entrance, non-fused design has a 3-pole mechanism with an unswitched neutral and a NEMA 3R steel enclosure specified for indoor or outdoor use.
The Generac RTSN400J3 is a 400 A automatic transfer switch for 120/240 V three-phase systems, with open-transition operation. Its non-service-entrance, non-fused design has a 3-pole mechanism with an unswitched neutral and a NEMA 3R steel enclosure specified for indoor or outdoor use.
Product information and specifications for the selected item.
| Brand | Generac |
|---|---|
| MPN | RTSN400J3 |
| SKU | RTSN400J3 |
| UPC / GTIN | 696471114430 |
| Category | Automatic Transfer Switches |
| Maximum Amperage (A) | 400 |
|---|---|
| Fused | Non-Fused |
| Automatic/Manual | Automatic |
| Maximum Amperage (A) | 400 |
|---|---|
| Fused | Non-Fused |
| Auxiliary contact rating | 10 amps at 125 or 250 volts AC |
| Equipment-load rating | 100% equipment-rated |
| Withstand rating | 35,000 A |
| Power-conductor range | (1) #4-600 MCM conductor or (2) 1/0-250 MCM conductors |
| Power terminal type | Solderless, screw-type terminal lugs are standard |
| Recommended control-wire sizes by length | No. 18 AWG for 1-115 ft; No. 16 AWG for 116-185 ft; No. 14 AWG for 186-295 ft; No. 12 AWG for 296-460 ft |
| Control wiring connections | Utility 1 and 2, and leads 23 and 194; run control interconnection leads in a conduit separate from the AC power lead |
| Pole and neutral configuration | 3-pole mechanism; three-phase neutral is not switched |
| Neutral switching | Neutral connects to a neutral lug and is not switched |
| Automatic/Manual | Automatic |
|---|---|
| Features | Mountable, Water Resistant |
| Enclosure material and finish | Steel enclosure with electrostatically applied and baked powder paint |
| Engine warmup delay | 5 s |
| Controller location | At the generator |
| Standby voltage sensor | 60% for 5 seconds |
| Load transition type | Open transition |
| Main-contact material | Silver-plated or silver alloy |
| Exerciser schedule | Nexus: 12 minutes weekly; Evolution: adjustable 5-12 minutes, weekly/bi-weekly/monthly |
| Control-system architecture | The generator controller handles timing, sensing, exercising, and transfer commands |
| Mounting guidance | Typically wall-mounted; mount vertically to a rigid supporting structure |
| Engine cooldown timer | 60 s |
| Retransfer delay | 15 s |
| Generator-start delay | 10 seconds factory-set; adjustable from 2 to 30 seconds by a qualified dealer with Evolution-control units |
| Transfer time | 160 ms |
| Height (in.) | 36.1 |
|---|---|
| Width (in.) | 24 |
| Length (in.) | 10 |