Generac GenReady 200A Service-Entrance-Rated Automatic Transfer Switch with 42-Space Load Center

0 Reviews
SKU
RXG42SHA1

The Generac RXG42SHA1 combines a service-entrance-rated automatic transfer switch with a 200 A main breaker and an integrated 120/240 V single-phase load center. The load center has 42 spaces and can be expanded to 60 circuits with tandem breakers; the non-fused assembly has an indoor Type 1 enclosure and manages up to four HVAC loads through 24 VAC contacts. It is specified for optional standby systems.

  • 200 A Automatic Transfer Switch
  • 120/240 V Single-Phase
  • 42-Space Load Center
  • Non-Fused Design
  • Indoor Type 1 Enclosure
  • Four-Load HVAC Management

The Generac RXG42SHA1 combines a service-entrance-rated automatic transfer switch with a 200 A main breaker and an integrated 120/240 V single-phase load center. The load center has 42 spaces and can be expanded to 60 circuits with tandem breakers; the non-fused assembly has an indoor Type 1 enclosure and manages up to four HVAC loads through 24 VAC contacts. It is specified for optional standby systems.

Product Overview

The Generac RXG42SHA1 combines a service-entrance-rated automatic transfer switch with a 200 A main breaker and an integrated 120/240 V single-phase load center. The load center has 42 spaces and can be expanded to 60 circuits with tandem breakers; the non-fused assembly has an indoor Type 1 enclosure and manages up to four HVAC loads through 24 VAC contacts. It is specified for optional standby systems.

  • 200 A Automatic Transfer Switch
  • 120/240 V Single-Phase
  • 42-Space Load Center
  • Non-Fused Design
  • Indoor Type 1 Enclosure
  • Four-Load HVAC Management

Technical Specifications

Product information and specifications for the selected item.

SKU: RXG42SHA1

Product Information

BrandGenerac
MPNRXG42SHA1
SKURXG42SHA1
UPC / GTIN696471069860
CategoryAutomatic Transfer Switches

Key Specs

Maximum Amperage (A)200
FusedNon-Fused
Automatic/ManualAutomatic

Electrical Ratings

Maximum Amperage (A)200
FusedNon-Fused
Ground connection torque50 in-lb
Phase and neutral configurationSingle-phase; neutral connects to a neutral lug and is not switched.
Generator/load connection conductor range and torque#6–250 MCM Cu/Al; 275 in-lb (31.0 N·m)
Utility connection conductor range and torque#1–300 MCM Cu/Al; 250 in-lb (28.2 N·m)
Short-circuit current rating (breaker-dependent)22 kA with Siemens/Murray branch breakers; 10 kA with Eaton/Square D Homeline branch breakers, at 240 VAC maximum kA RMS symmetrical
Frequency60 Hz
Branch-breaker compatibilityOne-inch Siemens, Murray, Eaton, or Square D Homeline breakers; for branch circuits and feeders over 50 A, only listed Siemens or Murray breakers.
Utility lug conductor range#1–300 MCM CU/AL
System voltage120/240 VAC
Neutral conductor range and torque#4–2/0; 40–50 in-lb (4.5–5.6 N·m)
Utility lug conductor temperature rating75 °C
Voltage and phase120/240 V, single-phase
Utility connection tightening torque250 in-lb
Utility-service short-circuit withstand capability22,000 A RMS symmetrical at 240 VAC max with Siemens/Murray branch breakers; 10,000 A RMS symmetrical at 240 VAC max with Eaton/Square D Homeline branch breakers
Panelboard ground-bar conductor terminations(2) or (3) 14 AWG, or (2) 12–10 AWG; 20 in-lb (2.3 N·m)

Transfer & Features

Automatic/ManualAutomatic
FeaturesMountable, On Indicator Light, Overload Protection
Smart A/C module contact rating and operationA/C 1–4 contacts: 24 VAC, 1.0 A maximum; normally closed and open on load-shed conditions
Enclosure typeType 1 enclosure; indoor installation only
Smart A/C module load-management capacityUp to four air-conditioner loads, arranged in four priority levels
Auxiliary contact configuration and ratingOne normally closed auxiliary contact; closed in utility mode and open in standby mode; rated 10 A at 125 or 250 VAC, or 0.6 A at 125 VDC
Generator control wiringClass 1 signaling circuit; recommended wire sizes are 18 AWG for 1–115 ft, 16 AWG for 116–185 ft, 14 AWG for 186–295 ft, and 12 AWG for 296–460 ft.
Intended system applicationFor optional standby systems only (NEC Article 702)
Load-shed frequency thresholdsLoads shed below 58 Hz for 3 seconds or below 50 Hz for 0.5 seconds (60 Hz systems)
Load types and application limitsSuitable for motor, electric-discharge-lamp, tungsten-filament, and electric-heating loads; combined motor and other load current must not exceed the switch rating, and tungsten load must not exceed 30% of the switch rating.
Mounting orientationTypically wall-mounted; mount vertically to a rigid supporting structure.

Dimensions & Weight

Height (in.)59.09
Width (in.)15.5
Length (in.)4.81
Weight (lb.)64

Product Documents

  • Schematic Diagram — Transfer Switch RXG 100–200A (Drawing No. 10000012595) Drawing photometric Open / download file
  • General Assembly Drawing — ASSY XFER SW 200A N1 ILC 42 CIRC (Drawing No. 10000011558) Drawing photometric Open / download file
  • Generac Power Systems Limited 5 Year (5M) Warranty for Stationary Transfer Switch Systems Warranty Open / download file
  • Owner’s Manual for Automatic Transfer Switch with Integrated Load Center — RXG24SHA1 / RXG42SHA1, Part No. 10000012870 Rev. B Manual Open / download file

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.