Generac RTSN100J3 100A 120/240V 3-Phase Non-Service-Entrance Automatic Transfer Switch
0 Reviews
SKU
RTSN100J3
Generac's RTSN100J3 is a 100 A automatic, open-transition transfer switch rated 120/240 V, three-phase. It is non-service-entrance and non-fused, with a water-resistant steel NEMA 3R enclosure for indoor and outdoor use.
100 A, 120/240 V Three-Phase
Automatic Open-Transition Operation
Non-Service-Entrance, Non-Fused
Steel NEMA 3R Enclosure
All Load Classes
UL and cUL Listed
Generac's RTSN100J3 is a 100 A automatic, open-transition transfer switch rated 120/240 V, three-phase. It is non-service-entrance and non-fused, with a water-resistant steel NEMA 3R enclosure for indoor and outdoor use.
Generac's RTSN100J3 is a 100 A automatic, open-transition transfer switch rated 120/240 V, three-phase. It is non-service-entrance and non-fused, with a water-resistant steel NEMA 3R enclosure for indoor and outdoor use.
100 A, 120/240 V Three-Phase
Automatic Open-Transition Operation
Non-Service-Entrance, Non-Fused
Steel NEMA 3R Enclosure
All Load Classes
UL and cUL Listed
Technical Specifications
Product information and specifications for the selected item.
SKU: RTSN100J3
Product Information
Brand
Generac
MPN
RTSN100J3
SKU
RTSN100J3
UPC / GTIN
696471110432
Category
Automatic Transfer Switches
Key Specs
Maximum Amperage (A)
100
Fused
Non-Fused
Automatic/Manual
Automatic
Certifications and Listings
cUL Listed, UL Listed
Electrical Ratings
Maximum Amperage (A)
100
Fused
Non-Fused
Load rating
All load classes; 100% equipment-rated for inductive and resistive loads
Lug range
2/0 - #6
Terminal lug construction
Solderless, screw-type terminal lugs
Voltage and phase
120/240 3Ø V
Withstand rating
14,000 A
Transfer & Features
Automatic/Manual
Automatic
Features
Water Resistant
Load transition type
Open transition
Utility voltage drop-out threshold
<60 %
Enclosure material
Steel
Contact mechanism
Electrically operated; mechanically held
Standby voltage sensor
60% for 5 seconds
Main contact material
Silver plated or silver alloy
Generator start delay
10 seconds factory-set; adjustable 2–30 seconds by a qualified dealer when used with Evolution controls
Neutral switching
The three-phase neutral connects to a neutral lug and is not switched