Skip to content

Generac RTSN200G3 200A 120/208V 3-Phase Automatic Transfer Switch, NEMA 3R

0 Reviews
SKU
RTSN200G3

The Generac RTSN200G3 is a 200 A automatic transfer switch for 120/208 V three-phase systems. It is non-fused and non-service-entrance-rated, with a heavy-duty contactor in a water-resistant NEMA 3R steel enclosure.

  • 200 A Rating
  • 120/208 V Three-Phase
  • Automatic Transfer Operation
  • NEMA 3R Water-Resistant Enclosure
  • Non-Service-Entrance-Rated and Non-Fused
  • UL and cUL Listed

Product Overview

The Generac RTSN200G3 is a 200 A automatic transfer switch for 120/208 V three-phase systems. It is non-fused and non-service-entrance-rated, with a heavy-duty contactor in a water-resistant NEMA 3R steel enclosure.

Technical Specifications

Product information and specifications for the selected item.

SKU: RTSN200G3

Product Information

BrandGenerac
MPNRTSN200G3
SKURTSN200G3
CategoryAutomatic Transfer Switches

Key Specs

Maximum Amperage (A)200
FusedNon-Fused
Automatic/ManualAutomatic
Certifications and ListingscUL Listed, UL Listed

Electrical Ratings

Maximum Amperage (A)200
FusedNon-Fused
Load rating basis100% equipment rated
Withstand rating25,000 A
Pole count3 poles
System voltage and phase120/208 V, 3-phase
Terminal typeSolderless, screw-type terminal lugs
Lug conductor range#4 to 400 MCM AWG/MCM
Service ratingNon-service rated
Neutral switchingThree-phase neutral connects to a neutral lug and is not switched.
Service entrance ratingNon-service-entrance rated

Transfer & Features

Automatic/ManualAutomatic
FeaturesWater Resistant
Control wire size by run length1–115 ft: 18 AWG; 116–185 ft: 16 AWG; 186–295 ft: 14 AWG; 296–460 ft: 12 AWG
Control wiring conduit requirementControl interconnection leads require separate conduit from AC power leads
Conduit entriesThree Triple EKO conduit-entry locations, suitable for 1, 1.25, or 1.50 in. conduit
Required electrical clearanceAt least 1/2 in. between live metal parts and grounded metal
Live-to-grounded metal clearanceAt least 1/2 in
Transfer time160 ms
Control wiring routingRun Utility 1 and 2 and leads 23 and 194 in a conduit separate from the AC power lead
Timing and sensing controller locationController at the generator
Load transition typeOpen transition
Mounting orientationMount vertically on a rigid supporting structure; level all mounting points
Enclosure material and finishSteel enclosure with electrostatically applied, baked powder paint

Certifications

Certifications and ListingscUL Listed, UL Listed

Dimensions & Weight

Height (in.)24.1
Width (in.)20.2
Length (in.)7.1
Weight (lb.)48
Mounting holesFour mounting holes, Ø0.25 in (6.35 mm) in (mm)

Product Documents

  • Generac Power Systems Two-Year Limited Warranty for Stationary Emergency Transfer Switch Systems Warranty Open / download file
  • RTS Automatic Transfer Switch Technical Manual (0F6139 Rev. H) Manual Open / download file
  • 3-Phase Sensing Wire Upgrade Power Zone 410 Kit — Instruction Sheet (G0074110; A0003140507 Rev. B) Installation manual Open / download file
  • 100–400 Amps Three Phase Automatic Transfer Switches (Non-Service Rated) Spec sheet Open / download file

Your cart

0 products 0 units

Your cart is empty.