Generac RTSN400K3 400A 277/480V 3-Phase Automatic Transfer Switch

0 Reviews
SKU
RTSN400K3

The Generac RTSN400K3 is a 400 A automatic transfer switch for 277/480 V three-phase standby power systems. It uses open-transition transfer and has a non-fused, non-service-entrance-rated design in a steel NEMA 3R enclosure specified for indoor or outdoor use.

  • 400 A capacity
  • 277/480 V, three-phase
  • Automatic open-transition operation
  • Non-service-entrance rated
  • Steel NEMA 3R enclosure
  • Non-fused, 3-pole configuration

Product Overview

The Generac RTSN400K3 is a 400 A automatic transfer switch for 277/480 V three-phase standby power systems. It uses open-transition transfer and has a non-fused, non-service-entrance-rated design in a steel NEMA 3R enclosure specified for indoor or outdoor use.

Technical Specifications

Product information and specifications for the selected item.

SKU: RTSN400K3

Product Information

BrandGenerac
MPNRTSN400K3
SKURTSN400K3
UPC / GTIN696471611885
CategoryAutomatic Transfer Switches

Key Specs

Maximum Amperage (A)400
FusedNon-Fused
Automatic/ManualAutomatic
Certifications and ListingscUL Listed, UL Listed

Electrical Ratings

Maximum Amperage (A)400
FusedNon-Fused
Withstand rating35,000 A
Load rating and supported load typesRated for all load classes; 100% equipment-rated for inductive and resistive loads
Power conductor range(1) #4–600 MCM or (2) 1/0–250 MCM
Terminal lug conductor range600 MCM - #4 or 1/0 - 250 MCM
Control lead wire-size schedule1–115 ft: 18 AWG; 116–185 ft: 16 AWG; 186–295 ft: 14 AWG; 296–460 ft: 12 AWG
Pole and neutral configuration3-pole mechanism; neutral connects to a neutral lug and is not switched
Power terminal typeSolderless, screw-type terminal lugs are standard
Auxiliary contact rating10 A at 125 or 250 VAC

Transfer & Features

Automatic/ManualAutomatic
FeaturesMountable, On Indicator Light, Water Resistant
Standby voltage sensor60% for 5 seconds
Timing and sensing control locationAll timing and sensing functions originate in the generator controller
Re-transfer time delay15 s
Generator-start delay10 s factory-set; adjustable from 2–30 s by a qualified dealer when used with Evolution controls
Main contact materialSilver-plated or silver-alloy main contacts
Control-wire conduit routingControl interconnection leads must run in a conduit separate from the AC power lead
Load transition typeOpen transition
Exerciser scheduleNexus: 12 minutes weekly; Evolution: 5–12 minutes adjustable, weekly/bi-weekly/monthly
Engine cooldown timer60 s
Control interconnection leadsUTILITY 1 and 2, and leads 23 and 194
Enclosure material and finishSteel enclosure with electrostatically applied and baked powder paint
Utility voltage pickup>80 %
Contact actuationElectrically operated, mechanically held contacts
Engine warmup delay5 s

Certifications

Certifications and ListingscUL Listed, UL Listed

Dimensions & Weight

Height (in.)48.1
Width (in.)30.1
Length (in.)13.1
Weight (lb.)133
Minimum live-to-ground clearanceAt least 1/2 in
Mounting orientationMount vertically on a rigid supporting structure

Product Documents

  • RTS Interconnection Diagram — Drawing No. 0F6689 Drawing photometric Open / download file
  • Build America, Buy America-Compliant Transfer Switches for the Wisconsin Refueling Readiness Program Certification compliance Open / download file
  • Generac Power Systems Two-Year Limited Warranty for Stationary Emergency Transfer Switch Systems — 0K3102 Rev. C Warranty Open / download file
  • Owner’s Manual — 400 Amp RTS Automatic Transfer Switch — Part 0F6351 Rev. D Manual Open / download file
  • RTS Automatic Transfer Switch Owner’s Manual — Part 0F6139 Rev. H Manual Open / download file
  • Non-Service Rated Automatic Transfer Switches, 100–400 Amps, Three Phase — 0186650SBY Rev. N Spec sheet Open / download file