Skip to content

Generac RXG16EZA3 100A 16-Circuit Automatic Transfer Switch, 120/240V, NEMA 3R, Integrated Load Center

0 Reviews
SKU
RXG16EZA3

Generac’s RXG16EZA3 is an automatic 100 A, single-phase 120/240 V transfer switch with an integrated 16-space load center in a NEMA 3R enclosure. The load center can expand to 24 circuits with tandem breakers, and the switch is specified for optional standby systems only.

  • 100 A automatic transfer switch
  • Single-phase 120/240 V
  • Integrated 16-space load center
  • Expandable to 24 circuits
  • NEMA 3R enclosure
  • One-inch breaker compatibility

Product Overview

Generac’s RXG16EZA3 is an automatic 100 A, single-phase 120/240 V transfer switch with an integrated 16-space load center in a NEMA 3R enclosure. The load center can expand to 24 circuits with tandem breakers, and the switch is specified for optional standby systems only.

Technical Specifications

Product information and specifications for the selected item.

SKU: RXG16EZA3

Product Information

BrandGenerac
MPNRXG16EZA3
SKURXG16EZA3
UPC / GTIN696471069907
CategoryAutomatic Transfer Switches

Key Specs

Maximum Amperage (A)100
Maximum Wattage (W)16000
Automatic/ManualAutomatic
Certifications and ListingsUL Listed

Electrical Ratings

Maximum Amperage (A)100
Maximum Wattage (W)16000
Control-module replacement fuse rating6.3 A, 240 VAC, 10,000 AIC
Tandem breaker capacity8 tandems
Power-lug tightening torque50 in-lb (5.6 Nm)
Auxiliary-contact rating10 A at 125 or 250 VAC; 0.6 A at 125 VDC
Power-lug temperature rating167 °F (75°C)
Available fault-current suitability10,000 symmetrical A
Neutral and ground bar conductor range#4–#14 AWG Cu/Al
Power-terminal conductor range#14–1/0 AWG (Cu/Al)
Generator-control terminal conductor materialCopper conductors only
Generator-control screw torque3.5 in-lb (0.4 Nm)
Supported load types and limitsSuitable for motors, electric-discharge lamps, tungsten-filament and electric-heating loads; tungsten load must not exceed 30% of switch rating, and total load must remain within switch rating
Withstand rating10,000 A
Generator-control wire size and runNo. 18 AWG minimum; up to 500 ft (152.4 m)
Generator-control circuit classificationClass 1 signaling circuit

Transfer & Features

Automatic/ManualAutomatic
FeaturesMountable, Water Resistant
Branch-circuit expansionExpandable to 24 circuits using tandem breakers in the bottom four positions
Power-terminal constructionSolderless, screw-type terminal lugs
Breaker size and over-50-A compatibilityOne-inch breakers; for branch circuits over 50 A, use only listed Siemens or Murray breakers.
Neutral configurationSingle-phase; neutral connects to a neutral lug and is not switched
Utility-restoration sequence timingRetransfer after approximately 15 s; engine shutdown approximately 1 min after retransfer
Compatible circuit breakersOne-inch breakers: Siemens, Murray, Eaton, or Square D; Siemens/Murray GFCI, AFCI, and tandem types up to 50 A; above 50 A, listed Siemens or Murray only
Standby applicationFor optional standby systems only (NEC Article 702)
Factory-default outage-to-standby timing10 s after utility loss before engine start (factory default); 5 s after generator start before standby transfer
Enclosure weather protectionDegree of protection against falling rain and sleet; undamaged by ice formation

Certifications

Certifications and ListingsUL Listed

Dimensions & Weight

Height (in.)30.1
Width (in.)13.5
Length (in.)6.91
Weight (lb.)39
Conduit knockout sizes1-1/2 and 2 in

Product Documents

  • Load Center Assembly — 16 Circuit, 3R Enclosure (Drawing No. 10000010468) Drawing photometric Open / download file
  • Wiring Diagram — HSB Transfer Switch 100A (Drawing No. 10000019053) Drawing photometric Open / download file
  • Schematic Diagram — HSB Transfer Switch 100A (Drawing No. 10000018987) Drawing photometric Open / download file
  • Interconnection Drawing — 3R 16 Circuit (Drawing No. 10000016945) Drawing photometric Open / download file
  • Generac Power Systems Limited 5 Year (5M) Warranty for Stationary Transfer Switch Systems (0K9470) Warranty Open / download file
  • Owner’s Manual for Automatic Transfer Switch, 100 Amp — RXG16EZA3 (Part No. 10000012410) Manual Open / download file

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.