Skip to content
Gillette Generators

Gillette SP-2000 200kW Natural Gas Standby Generator, 120/208VAC, 3-Phase, Level 2 Aluminum Enclosure

0 Reviews
SKU
SP-2000-3-2N2

The Gillette Generators SP-2000-3-2N2 is a commercial standby generator rated for 200 kW (250 kVA), with natural gas fuel and 120/208 VAC, three-phase, 60 Hz output. It has a Level 2 sound- and weather-protected aluminum enclosure.

  • 200 kW / 250 kVA Standby Output
  • 120/208 VAC Three-Phase Output
  • Natural Gas Fuel
  • 694 A Output Amperage
  • 11.1 L Liquid-Cooled PSI Engine
  • Level 2 Aluminum Enclosure

The Gillette Generators SP-2000-3-2N2 is a commercial standby generator rated for 200 kW (250 kVA), with natural gas fuel and 120/208 VAC, three-phase, 60 Hz output. It has a Level 2 sound- and weather-protected aluminum enclosure.

Product Overview

The Gillette Generators SP-2000-3-2N2 is a commercial standby generator rated for 200 kW (250 kVA), with natural gas fuel and 120/208 VAC, three-phase, 60 Hz output. It has a Level 2 sound- and weather-protected aluminum enclosure.

  • 200 kW / 250 kVA Standby Output
  • 120/208 VAC Three-Phase Output
  • Natural Gas Fuel
  • 694 A Output Amperage
  • 11.1 L Liquid-Cooled PSI Engine
  • Level 2 Aluminum Enclosure

Technical Specifications

Product information and specifications for the selected item.

SKU: SP-2000-3-2N2

Product Information

BrandGillette Generators
MPNSP-2000-3-2N2
SKUSP-2000-3-2N2
CategoryCommercial Standby Generators

Key Specs

Running Wattage200000 W
Amperage (A)694
Output Voltage120/208 VAC
Electrical Phases3
Fuel TypeNatural Gas
LP Power Capacity136

Generator Output

Running Wattage200000 W
Amperage (A)694
Output Voltage120/208 VAC
Electrical Phases3
Winding configuration and power factor12-lead winding; rated power factor 0.8
Total harmonic distortionMaximum 3½ %
Voltage and frequency regulationVoltage: ½% no-load to full-load; frequency: ½% (½ cycle) no-load to full-load
Motor-starting capability620 at 30% voltage dip (208–240 V) kVA
Standby overload capabilityNo overload capability during a utility outage
Frequency conversionField-convertible from 60 to 50 Hz
Environmental deratingAltitude: 3% per 1,000 ft above 3,000 ft (914 m); temperature: 2% per 10°F (5.6°C) above 104°F (40°C)
Winding insulation systemClass H (180) insulation on rotor and stator windings °C

Fuel Capacity

Fuel TypeNatural Gas
LP Power Capacity136
NG Power Capacity200
Natural-gas consumption at standby load100% load: 2,115 (59.9); 75% load: 1,649 (46.7); 50% load: 1,158 (32.8) ft³/h (m³/h)
Fuel pressure7–11 (1.74–2.74) in. H₂O (kPa)
Natural-gas fuel consumption at full load2,115 at 100% load (59.9) ft³/hr (m³/hr)

Engine & Cooling

Engine BrandPSI
Cooling TypeLiquid Cooled
RPM1800 rpm
Exhaust conditions3.5-in exhaust outlet; rated exhaust flow 1,425 cfm (40.3 m³/min) and temperature 1,382°F (750°C)
Airflow requirementsCombustion air: 448 cfm (12.7 m³/min); radiator airflow: 18,000 cfm (510 m³/min)
Engine displacement and configuration674 cu in (11.1 L); 4-cycle, 6-cylinder inline, turbocharged and charge-air cooled
Low-load operating guidanceLimit low-load operation to no more than 1 hour per 24 hours; for extended light-load operation, reach at least 70% of mechanical rating for at least 2 hours per 50 hours of low-load operation
Starting battery requirementTwo 12 VDC BCI #27 batteries in series for a 24 VDC starting system
Compression ratio10.5:1
Coolant-temperature shutdown setting230°F (110°C) with a 50/50 water/antifreeze mixture °F (°C)

Features & Connections

Generator FeaturesAutomatic Voltage Regulation, Hour Meter, Low Oil Alert/Shutdown
FeaturesCARB approved, EPA Compliant, Made in America
Approved for Commercial UseYes
Enclosure corrosion protection9 heated and agitated wash stages; zinc-phosphate etching-coating; baked-on enamel powder coat; 18/8 stainless-steel hardware
NFPA-110 levelNFPA-110 Level 1 when equipped with necessary accessories and installed per NFPA standards
Fuel supply inlet connection2 in. NPTF
Wind rating180 mph
UL standards referencedUL 2200, UL 1446, UL 508, UL 142, UL 498
Sound level, Level 2 enclosure75 with the Level 2 critical silencer at 23 ft (7 m) dB(A)

Product Documents