The Global Power Products NE-5000 is an energy submeter for energy-consumption monitoring, with a 2500 A primary current rating and three supplied split-core CTs. It uses Ethernet communication and has a NEMA 4X enclosure rating and Class 0.5 accuracy.

  • 2500 A primary current
  • Three split-core CTs
  • Ethernet communication
  • Class 0.5 accuracy
  • NEMA 4X enclosure
  • Multiple service configurations

The Global Power Products NE-5000 is an energy submeter for energy-consumption monitoring, with a 2500 A primary current rating and three supplied split-core CTs. It uses Ethernet communication and has a NEMA 4X enclosure rating and Class 0.5 accuracy.

Product Overview

The Global Power Products NE-5000 is an energy submeter for energy-consumption monitoring, with a 2500 A primary current rating and three supplied split-core CTs. It uses Ethernet communication and has a NEMA 4X enclosure rating and Class 0.5 accuracy.

  • 2500 A primary current
  • Three split-core CTs
  • Ethernet communication
  • Class 0.5 accuracy
  • NEMA 4X enclosure
  • Multiple service configurations

Technical Specifications

Product information and specifications for the selected item.

SKU: NE-5000-2500A-ETHERNET

Product Information

BrandGlobal Power Products
MPNNE-5000-2500A-ETHERNET
SKUNE-5000-2500A-ETHERNET
CategoryMetering Equipment

Key Specs

Monitoring Primary Rated Current2500 A
Monitoring Accuracy ClassClass 0.5
NEMA Enclosure RatingNEMA 4X

Monitoring & Electrical

Monitoring Primary Rated Current2500 A
Current-circuit burden1 VA max (phases A, B, C)
Power-circuit burden0.24 VA max (phases B and C)
Voltage-circuit burden8.6 VA max (phase A)
Frequency operating range47 to 63 Hz

Configuration & Interface

ComponentEnergy Meter
Monitoring TypeEnergy Consumption
Monitoring Connection MethodEthernet
Terminal conductor size18–14 AWG copper
Phase-lead matchingMatch each phase's voltage tap to the corresponding current-transformer leads
CT lead splice routingKeep CT-lead splices inside the meter enclosure and outside the conduit
CT reassemblyReassemble the CT in the same configuration after disassembly
Acceptable service configurations3-phase 4-wire Wye/Delta; 3-phase 3-wire Delta; 1-phase 2-wire or 3-wire
Diagnostic test mode accessAccessible with a 30-gauss magnet near the reed switch
Terminal tightening torque6 lb-in
Network metering-point capacityUp to 1000 metering points
CT polarity orientationCT polarity dot faces the line or supply side

Ratings & Approvals

NEMA Enclosure RatingNEMA 4X
Monitoring Accuracy ClassClass 0.5
Monitoring ApprovalANSI C12.20, ANSI C37.90.1, UL
Operating temperature range-40 to +85 °C
Relative humidity range0 to 95, non-condensing %
Installation overvoltage categoryCategory III
Measurement categoryCategory III
Pollution degreeDegree 2
Insulation/surge-performance standardANSI/IEEE C37.90.1-1989
Maximum altitude2000 maximum

Dimensions & Weight

CT clearance from line terminalsThe CT body must not contact the panel line terminals
Conduit entryOne bottom enclosure hole accommodates 3/4-inch conduit in.
Enclosure mounting tabsThree mounting tabs on the back of the enclosure
CT panel wiring-space limitDo not install where CTs exceed 75% of wiring space at any panel cross-section