Skip to content

HF363N Heavy-Duty Fusible Safety Switch, 100A, 3P/4W, 600V, NEMA Type 1

0 Reviews
SKU
HF363NA

The Siemens HF363NA is a 100 A, 3-pole, 600 V fused heavy-duty indoor safety switch with mechanical lugs. It has a double-break visible-blade design and is specified as suitable for service-entrance equipment.

  • 100 A, 3-Pole, 600 V
  • Fuse-Dependent Short-Circuit Ratings
  • AC/DC Motor Horsepower Ratings
  • Mechanical Lugs and Wire Range
  • Service-Entrance Suitability
  • Line-Side Barrier Shields

The Siemens HF363NA is a 100 A, 3-pole, 600 V fused heavy-duty indoor safety switch with mechanical lugs. It has a double-break visible-blade design and is specified as suitable for service-entrance equipment.

Product Overview

The Siemens HF363NA is a 100 A, 3-pole, 600 V fused heavy-duty indoor safety switch with mechanical lugs. It has a double-break visible-blade design and is specified as suitable for service-entrance equipment.

  • 100 A, 3-Pole, 600 V
  • Fuse-Dependent Short-Circuit Ratings
  • AC/DC Motor Horsepower Ratings
  • Mechanical Lugs and Wire Range
  • Service-Entrance Suitability
  • Line-Side Barrier Shields

Technical Specifications

Product information and specifications for the selected item.

SKU: HF363NA

Product Information

BrandSiemens
SKUHF363NA
CategoryDisconnects & Safety Switches

Key Specs

Maximum Amperage (A)100
Maximum Wattage (W)0
Phase Type3 Phase
Disconnect TypeSafety Switch
NEMA Enclosure RatingNEMA 1

Switch Ratings

Maximum Amperage (A)100
Maximum Wattage (W)0
Phase Type3 Phase
Typical mechanical service life10,000 cycles
DC short-circuit rating100,000 with Class R or J fuses at 600 V DC AIC
Overload current rating12Ă— overload current rating, exceeding the 10Ă— industry standard
Horsepower ratings480 V AC, 3-phase: 25 standard/60 max; 600 V AC, 3-phase: 30 standard/75 max; 600 V DC: 25; additionally 20 at 250 V DC hp
Horsepower rating conditionsStandard ratings apply with non-time-delay fuses; maximum ratings apply with time-delay fuses. Ratings also apply to Design E motors without derating.
I²t rating500,000 A²·s
Rated supply frequency50/60 Hz
AC short-circuit rating10,000 with Class H fuses; 200,000 with Class R, T, and J fuses AIC

Disconnect Configuration

Disconnect TypeSafety Switch
FusedFused
Mounting arrangement2- and 3-point mounting holes
Switching actionQuick-make and break switching action
Actuating elementSingle throw
Position indicationHighly visible ON/OFF indication
Fastening methodSurface
Cover interlockDefeatable dual cover interlock
Electrical connectionMechanical lugs
Mechanical lug wire rangeFor 60/75°C Cu/Al conductors: #12–1/0 AWG aluminum or #14–1/0 AWG copper
Blade designDouble-break visible blade design
Lug design and compatibilityFront-removable; convertible to copper-body or compression-type lugs
Ground conductor range#14–4 AWG

Enclosure & Certifications

NEMA Enclosure RatingNEMA 1
Certifications and ListingsUL Listed
Service-entrance suitabilitySuitable for use as service entrance equipment
Line-side barriersInternal shields meet 2020 NEC 230.62 line-side barrier requirements
Enclosure thickness0.054 (17 gauge) in
Enclosure materialCold-rolled steel
Enclosure finishANSI Grey #61 paint

Dimensions & Weight

Height (in.)23.15
Width (in.)12.01
Length (in.)10.17
Weight (lb.)20.81