Skip to content
Honeywell

Honeywell 60kW Liquid-Cooled Standby Generator, 120/240V Single-Phase, Mobile Link Wi-Fi

0 Reviews
SKU
HG06045ANAX

The Honeywell HG06045ANAX is a 60 kW liquid-cooled standby generator with 120/240 V single-phase output and natural gas or propane fuel. It uses a Generac 4.5 L turbocharged, aftercooled engine and includes Mobile Link Wi-Fi remote monitoring.

  • 60 kW Running Output
  • 120/240 V Single-Phase Output
  • Natural Gas or Propane
  • Liquid-Cooled System
  • Generac 4.5 L Engine
  • Mobile Link Wi-Fi Monitoring

The Honeywell HG06045ANAX is a 60 kW liquid-cooled standby generator with 120/240 V single-phase output and natural gas or propane fuel. It uses a Generac 4.5 L turbocharged, aftercooled engine and includes Mobile Link Wi-Fi remote monitoring.

Product Overview

The Honeywell HG06045ANAX is a 60 kW liquid-cooled standby generator with 120/240 V single-phase output and natural gas or propane fuel. It uses a Generac 4.5 L turbocharged, aftercooled engine and includes Mobile Link Wi-Fi remote monitoring.

  • 60 kW Running Output
  • 120/240 V Single-Phase Output
  • Natural Gas or Propane
  • Liquid-Cooled System
  • Generac 4.5 L Engine
  • Mobile Link Wi-Fi Monitoring

Technical Specifications

Product information and specifications for the selected item.

SKU: HG06045ANAX

Product Information

BrandHoneywell
MPNHG06045ANAX
SKUHG06045ANAX
CategoryResidential Standby Generators

Key Specs

Running Wattage60000 W
Popular Running Wattage60000 W
Power/Fuel TypeNatural Gas, Propane
Operational VolumeStandard (Above 60 dB)

Generator Output

Running Wattage60000 W
Popular Running Wattage60000 W
Power/Fuel TypeNatural Gas, Propane
Natural gas consumption at 100% rated load808 / 22.9 ftÂł/hr / mÂł/hr
Natural gas operating pressure3.5–14 / 0.87–3.48 in. water column / kPa
Surge capacity at 120/240 V single-phase150 A at 15% voltage dip; 413 A at 30% dip, at <0.4 power factor
Single-phase alternator output leads4-wire
Alternator typeSynchronous
Rotor and stator insulation classesRotor Class H; stator Class H
Minimum required fuel heating valueNatural gas ≥1,000 BTU/ft³; propane ≥2,520 BTU/ft³
Propane consumption at 100% rated load8.4 / 31.8 gal/hr / L/hr
Temperature derating1.65% per 10 °F above 77 °F; 3% per 10 °C above 25 °C
Altitude derating3% per 1,000 ft above 600 ft; 1% per 100 m above 183 m

Transfer & Application

ApplicationHome Standby
Combustion airflow at rated power170.4 / 4.8 scfm / cmm
Mounting fastener specification5/8-11 Grade 5 bolts or studs
Fuel line connection1-1/4 in. NPT female tee
Installation locationOutdoor installation only; factory-installed all-weather enclosure

Features & Operation

FeaturesAutomatic Voltage Regulation, Built-in Remote Monitoring, LCD Display, Low Oil Shutdown, Muffler
Operational VolumeStandard (Above 60 dB)
Rated synchronous speed1,800 rpm
Maximum ambient temperature140 °F
Recommended batteryGroup 27F, 725 CCA
Engine intake systemTurbocharged and aftercooled
System coolant capacity4.5 / 17 gal / L
Compression ratio8.85:1
Cooling system typeClosed
Enclosure material and finishAluminium; dark gray
Safety listingUL 2200 Listed

Dimensions & Weight

Minimum recommended concrete pad size50 in wide Ă— 110 in long

Product Documents

  • Owner’s Manual for Spark-Ignited Stationary Generators, Residential and Commercial (48 kW, 60 kW, 80 kW, 4.5L) Manual Open / download file
  • 48 / 60 / 80 kW Liquid-Cooled Generator Sets Spec sheet Open / download file