The IHI Connectors ML250 is a one-hole, tin-plated aluminum lug listed for 250 kcmil–6 AWG copper or aluminum conductors. The supplied product description states 600 V; detailed specifications list a 90°C conductor temperature rating and a 0.343-in mounting hole for a 5/16-in bolt.

  • 250 kcmil–6 AWG Conductor Range
  • Tin-Plated Aluminum Body
  • 600 V Rating
  • 90°C Conductor Temperature Rating
  • 0.343-in Mounting Hole
  • 3/8-in Hex Socket Screw

Product Overview

The IHI Connectors ML250 is a one-hole, tin-plated aluminum lug listed for 250 kcmil–6 AWG copper or aluminum conductors. The supplied product description states 600 V; detailed specifications list a 90°C conductor temperature rating and a 0.343-in mounting hole for a 5/16-in bolt.

Technical Specifications

Product information and specifications for the selected item.

SKU: ML250

Product Information

BrandIHI Connectors
SKUML250
CategoryLugs

Key Specs

Certifications and ListingsUL Listed
Height (in.)1.062
Width (in.)0.906

Electrical & Listings

Certifications and ListingsUL Listed
FLEX conductor limitationFLEX G–K conductors: single-wire use only
Conductor temperature rating90 °C
Flexible copper conductor ranges3/0–2 AWG (70–50 mm²) and 2–6 AWG (35–16 mm²).
Conductor size range250 kcmil–6 AWG (AL9CU)
Conductor range and material250 kcmil–6 AWG; copper or aluminum conductors
Conductor tightening torque, smaller wire ranges275 for copper, FLEX copper, and aluminum 2–6 AWG in-lb
Temperature rating90 °C
Conductor tightening torque, larger wire ranges375 for copper 250 kcmil–2 AWG, FLEX copper 3/0–2 AWG, and aluminum 250 kcmil–2 AWG in-lb
Wire termination torque375 in-lb for the 250 kcmil–2 AWG copper/aluminum group (3/0–2 AWG flexible copper); 275 in-lb for the 2–6 AWG group.
Multiple-wire capabilityTwo Class B/C conductors per barrel, 2–6 AWG; do not mix wire gauges
Material, finish and conductor useTin-plated aluminum for single copper or aluminum conductors.
FLEX stranding classesG, H, I/DLO, metric Class 5, and K/MTW
FLEX conductor range3/0–6 AWG FLEX copper
Flexible copper stranding classesG, H, I/DLO, metric Class 5, and K/MTW.
Voltage-tap ring-lug screw torque10–12 in-lb seating torque for the M3 × 8 mm screw.
Contact-face plating protectionProtect the tin-plated contact face during drilling; do not remove plating from the mating-busbar contact zone.
Voltage-tap ring-lug modificationThe chart permits a field location/voltage-tap hole for S250 styles where marked; the guide covers an M3 ring-lug tap for #14 (2.5 mm²) wire, for qualified electricians only.

Dimensions & Weight

Height (in.)1.062
Width (in.)0.906
Length (in.)2
Field mounting-hole options by styleField mounting-hole limits depend on style: styles 1–2 allow 1 hole, style 3 allows 1–2, and styles 4–5 allow 0–2, all at 13/64–17/32 in; style 6 allows 2–4 at 11/64–13/64 in and/or 1–2 at 1/4–3/8 in.
Screw type and hex size3/8-in hex socket screw
Mounting bolt size5/16 in
Mounting-hole type optionsThreaded and non-round (oval or elongated) mounting holes are permitted for S250 styles marked in the chart.
Voltage-tap hole preparationUse a 2.75 mm HSS twist drill to make a vertical hole 8.0 mm deep; no lubricant is needed.
Minimum end-wall dimension for field drillingMinimum end-wall dimension A for field drilling: 0.110 in (2.79 mm).
Mounting interfaceOne 0.343-in mounting hole for a 5/16-in (8-mm) bolt