ILSCO SK-1/0 CU Tin-Plated Copper Split-Bolt Connector
0 Reviews
SKU
SK-1/0 CU
The ILSCO SK-1/0 CU is a tin-plated copper split-bolt connector for two conductors, with UL and CSA listing information and documented copper and Copperweld conductor combinations.
Tin-Plated Copper Construction
Two-Conductor Split-Bolt Connector
Copper and Copperweld Combinations
35 kV Voltage Rating
90°C Temperature Rating
385 in-lb Recommended Torque
The ILSCO SK-1/0 CU is a tin-plated copper split-bolt connector for two conductors, with UL and CSA listing information and documented copper and Copperweld conductor combinations.
The ILSCO SK-1/0 CU is a tin-plated copper split-bolt connector for two conductors, with UL and CSA listing information and documented copper and Copperweld conductor combinations.
Tin-Plated Copper Construction
Two-Conductor Split-Bolt Connector
Copper and Copperweld Combinations
35 kV Voltage Rating
90°C Temperature Rating
385 in-lb Recommended Torque
Technical Specifications
Product information and specifications for the selected item.
Clean conductors with a wire brush or abrasive cloth; apply anti-oxidant to stripped ends and work it into the wire strands with a brush.
Recommended tightening torque
385 in-lb
NEC wire stripping condition
For insulated 90°C-maximum-rated wire in NEC applications, strip immediately before installation.
Direct burial
No
Main drive type
External hex
Material
Copper
Splice connection installation
Insert wires through opposite sides to full clamp contact; hand-tighten the nut, then torque to the chart value.
UL/CULUS specification
UL 486A/B Listed
CSA standards
C22.2 No. 65; C22.2 No. 188
CSA mark identifier
701570
Maximum conductor diameter
0.375 in
Tap size with one maximum main
10 solid AWG
Spacer placement and orientation
For SK models, always position and clamp the additional spacer between the two wires, with its radius side facing the nut/pressure bar.
Tap connection installation
For a tap connection, remove the nut/pressure bar and spacer, position the connector over the main wire, reinstall the spacer and nut/pressure bar, insert the tap to full clamp contact, then hand-tighten and torque.
Insulation stripping
Strip enough insulation for clamping contact without overlap, and avoid nicking wire strands; use an appropriate stripping tool or pencil-shaving method.
Torque-related hazard
Failure to achieve proper torque can cause connector and wire overheating.