Skip to content
Kohler

Kohler 26RCA-QS2 120/208V 3-Phase Standby Generator

0 Reviews
SKU
26RCA-QS2

The KOHLER 26RCA-QS2 is an air-cooled commercial standby generator with 120/208 VAC three-phase output. It runs on natural gas or LPG, with stated fuel-specific output of 21 kW on natural gas and 22 kW on LPG, and uses a 999 cm³ V-twin engine in an aluminum enclosure.

  • 120/208 VAC, Three-Phase Output
  • 21 kW NG / 22 kW LPG Ratings
  • Air-Cooled 999 cm³ V-Twin Engine
  • Aluminum Enclosure
  • Low-Oil Alert/Shutdown, AVR & Hour Meter
  • 5-Year / 2,000-Hour Limited Warranty

The KOHLER 26RCA-QS2 is an air-cooled commercial standby generator with 120/208 VAC three-phase output. It runs on natural gas or LPG, with stated fuel-specific output of 21 kW on natural gas and 22 kW on LPG, and uses a 999 cm³ V-twin engine in an aluminum enclosure.

Product Overview

The KOHLER 26RCA-QS2 is an air-cooled commercial standby generator with 120/208 VAC three-phase output. It runs on natural gas or LPG, with stated fuel-specific output of 21 kW on natural gas and 22 kW on LPG, and uses a 999 cm³ V-twin engine in an aluminum enclosure.

  • 120/208 VAC, Three-Phase Output
  • 21 kW NG / 22 kW LPG Ratings
  • Air-Cooled 999 cm³ V-Twin Engine
  • Aluminum Enclosure
  • Low-Oil Alert/Shutdown, AVR & Hour Meter
  • 5-Year / 2,000-Hour Limited Warranty

Technical Specifications

Product information and specifications for the selected item.

SKU: 26RCA-QS2

Product Information

BrandKohler
MPN26RCA-QS2
SKU26RCA-QS2
CategoryCommercial Standby Generators

Key Specs

Running Wattage22000 W
Amperage (A)77
Output Voltage120/208 VAC
Electrical Phases3
Fuel TypeDual-Fuel (LP/NG)
LP Power Capacity22000

Generator Output

Running Wattage22000 W
Amperage (A)77
Output Voltage120/208 VAC
Electrical Phases3
One-step load acceptance100 % of rating
Winding material and treatmentCopper windings; vacuum-impregnated with epoxy varnish
Standby rating conditionsStandby rating applies to reliable-utility installations; variable loads average an 80% load factor during the outage; no overload capacity specified
Frequency regulation±0.5 steady-state %
Total harmonic distortionLess than 5 from no-load to full-load with a linear load %
Alternator model and lead count2F8; 4 leads
Altitude and temperature deratingAltitude: derate 4% per 305 m (1,000 ft.) above 153 m (500 ft.); temperature: derate 2% per 5.5°C (10°F) above 16°C (60°F)
Insulation class and temperature riseNEMA MG1-1.66, Class H; 130°C temperature rise at standby

Fuel Capacity

Fuel TypeDual-Fuel (LP/NG)
LP Power Capacity22000
NG Power Capacity21000
Fuel consumption at full load, 60 HzAt 100% load, natural gas: 8.2 m³/hr (290 cfh); LPG: 3.6 m³/hr (129 cfh). m³/hr (cfh)
Fuel supply pressureNatural gas: 3.5–11; LPG: 7–11 in. H2O
Fuel consumption at 50% loadNatural gas: 180; LPG: 85 at 50% load cfh
Fuel composition limitsNatural gas: methane ≥90 vol%, ethane ≤4.0%, propane ≤1.0%, propene ≤0.1%, C4+ ≤0.3%, minimum LHV 33.2 MJ/m³ (890 Btu/ft³). LPG: propane ≥85 vol%, propene ≤5.0%, C4+ ≤2.5%, minimum LHV 84.2 MJ/m³ (2260 Btu/ft³). Sulfur maximum 25 ppm by mass.
Fuel inlet connection3/4 NPT female
Minimum gas pipe size by line lengthNG 1 in. / LPG 3/4 in. at 25 ft; NG 1-1/4 in. / LPG 1 in. at 50–150 ft; NG 1-1/2 in. / LPG 1-1/4 in. at 200 ft in. NPT

Engine & Cooling

Engine BrandKohler
Cooling TypeAir Cooled
RPM3600 rpm
Engine configuration and displacementCH1006, four-cycle V-2; displacement 999 cm³ (61 cu. in.)

Features & Connections

Generator FeaturesAutomatic Voltage Regulation, Hour Meter, Low Oil Alert/Shutdown
FeaturesApproved for Commercial Use, CARB approved, EPA Compliant
Approved for Commercial UseYes
Standard warranty5-year/2,000-hour limited standby warranty; covers parts, labor, and travel
Wind rating181 mph
Starting battery requirement12 VDC negative-ground starting battery; Group 51; minimum 500 CCA at −18°C (0°F)
Listings and acceptancecULus listed; accepted by the Massachusetts Board of Registration of Plumbers and Gas Fitters
Standard enclosure finishCashmere (standard)
Enclosure foam specificationSound-deadening, flame-retardant foam; UL 94 class HF-1
Sound level56 during engine exercise; 67 during full-speed diagnostics and normal operation; measured at 23 ft (7 m) dB(A)
Installation environmentOutdoor installation only

Dimensions & Weight

Height (in.)32.3
Width (in.)26
Length (in.)47
Combustible-material clearance guideline18-inch NFPA guideline to combustible materials; verify required structure spacing with state and local codes in.

Product Documents