The Kohler RXT-JFTC-400A-MV06 is an automatic 400 A transfer switch specified for 120/240 V three-phase, 3-pole/4-wire service. It has a NEMA 3R aluminum enclosure for indoor or outdoor use and is compatible with Kohler generators equipped with RDC2 or DC2 controllers. The switch is UL Listed.

  • 400 A Maximum Amperage
  • 120/240 V, 3-Phase, 3P/4W
  • Kohler RDC2/DC2 Compatibility
  • NEMA 3R Aluminum Enclosure
  • Automatic Transfer Operation
  • UL Listed

Product Overview

The Kohler RXT-JFTC-400A-MV06 is an automatic 400 A transfer switch specified for 120/240 V three-phase, 3-pole/4-wire service. It has a NEMA 3R aluminum enclosure for indoor or outdoor use and is compatible with Kohler generators equipped with RDC2 or DC2 controllers. The switch is UL Listed.

Technical Specifications

Product information and specifications for the selected item.

SKU: RXT-JFTC-400A-MV06

Product Information

BrandKohler
MPNRXT-JFTC-400A-MV06
SKURXT-JFTC-400A-MV06
CategoryAutomatic Transfer Switches

Key Specs

Maximum Amperage (A)400
Automatic/ManualAutomatic
Certifications and ListingsUL Listed

Electrical Ratings

Maximum Amperage (A)400
Current derating100% equipment-rated; can be applied at rated current without derating for non-service-entrance models
Neutral conductor rangeCu/Al: (3) #4 AWG–600 kcmil or (6) 1/0 AWG–250 kcmil
Operating frequency60 Hz
Normal and emergency/load terminal conductor rangeCu/Al: (1) #4–600 kcmil or (2) 1/0–250 kcmil per phase
Undervoltage dropout threshold90% of pickup
Voltage sensing accuracy±5 %
Withstand and close-on rating (WCR)65,000 at 240 V A RMS symmetrical
Undervoltage pickup threshold90% of nominal
Ground conductor range(6) #6–3/0 AWG

Transfer & Features

Automatic/ManualAutomatic
Enclosure materialAluminum
Enclosure typeIndoor or Outdoor
Generator compatibilityAll KOHLER Generators with RDC2 or DC2 controllers
Load center configurationWithout load center
Humidity range5 to 95, noncondensing %
Auxiliary position-indicating contactsTwo normal and two emergency contacts standard; one additional normal and one emergency contact optional; rated 10 A at 480 VAC
Operating temperature range-20 to 70 °C
Load control delay5 (fixed; not adjustable) minutes
Main contact materialSilver alloy
Storage temperature range-40 to 85 °C
Controller interface A/B wiring#20 AWG shielded twisted pair; Belden 9402, 8762, or equivalent
Normal-to-emergency transfer delay3 seconds
Transfer switch typeStandard
Contactor interlockingElectrically and mechanically interlocked
Engine start delay3 seconds

Certifications

Certifications and ListingsUL Listed

Dimensions & Weight

Height (in.)48.1
Width (in.)24
Weight (lb.)104

Product Documents

  • Model RDT and RXT Transfer Switches, Five-Year Limited Warranty — United States (TP-7231) Warranty Open / download file
  • Service and Parts Manual, Automatic Transfer Switches, Model RXT, 100–400 Amps (TP-6808, 12/18) Manual Open / download file