Skip to content
Kohler

Kohler RXT 400A Outdoor Service-Entrance Automatic Transfer Switch, 240V Single-Phase

0 Reviews
SKU
RXT-JFNC-400ASEQS3

The Kohler RXT-JFNC-400ASEQS3 is a 400 A, 240 V single-phase automatic transfer switch compatible with single-phase KOHLER generators using RDC2 or DC2 controllers. It is service-entrance rated, UL Listed, and supplied without a load center.

  • 400 A, 240 V Single-Phase
  • Service-Entrance Rated
  • KOHLER Generator Compatibility
  • NEMA 3R Aluminum Enclosure
  • Manages Up to Six Residential Loads
  • UL Listed

Product Overview

The Kohler RXT-JFNC-400ASEQS3 is a 400 A, 240 V single-phase automatic transfer switch compatible with single-phase KOHLER generators using RDC2 or DC2 controllers. It is service-entrance rated, UL Listed, and supplied without a load center.

Technical Specifications

Product information and specifications for the selected item.

SKU: RXT-JFNC-400ASEQS3

Product Information

BrandKohler
MPNRXT-JFNC-400ASEQS3
SKURXT-JFNC-400ASEQS3
UPC / GTIN650531379023
CategoryAutomatic Transfer Switches

Key Specs

Maximum Amperage (A)400
Automatic/ManualAutomatic
Certifications and ListingsUL Listed

Electrical Ratings

Maximum Amperage (A)400
Wire count3 wires
Pole and wire configuration2-pole, 3-wire, solid neutral (120/240 V system)
Withstand and close-on rating35,000 RMS symmetrical A at 240 VAC
Neutral terminal wire range(12) 1/0-250 KCMIL or (6) #4 AWG-600 KCMIL AWG/kcmil
Normal-source terminal wire range(1) #1-600 KCMIL or (2) #1-250 KCMIL per phase AWG/kcmil
Rated frequency60 Hz
Continuous-load limitContinuous load current must not exceed 80% of switch rating
Emergency and load terminal wire range(2) 1/0-250 KCMIL or (1) #4-600 KCMIL per phase AWG/kcmil
Utility-source disconnectFactory-equipped utility-side disconnect circuit breaker; 80%-rated

Transfer & Features

Automatic/ManualAutomatic
FeaturesOverload Protection, Water Resistant
Storage temperature-40 to 85 (-40 to 185) °C (°F)
Installation environmentApproved for indoor or outdoor installation
Main contact materialSilver alloy
Load-control delay5; fixed and not adjustable minutes
Operating temperature-20 to 70 (-4 to 158) °C (°F)
Customer-supplied power relay modulesUp to 4 customer-supplied modules for non-essential secondary loads
Enclosure finishANSI 49 gray
Managed residential loadsUp to 6 residential loads
Compatible generator setsAll single-phase KOHLER generators with RDC2 or DC2 controllers
Engine-start delay3 seconds
Load centerNo load center
Normal-to-emergency transfer delay3 seconds
Enclosure constructionCorrosion-resistant NEMA 3R aluminum enclosure
Enclosure lockingPadlockable
Humidity5 to 95, noncondensing %

Certifications

Certifications and ListingsUL Listed

Dimensions & Weight

Height (in.)57.2
Width (in.)24.8
Weight (lb.)130

Product Documents

  • Model RDT and RXT Transfer Switches — Five-Year Limited Warranty, United States (TP-7231 1/24b) Warranty Open / download file
  • Service and Parts — Automatic Transfer Switches, Model RXT, 100–400 Amp (TP-6808 12/18c) Manual Open / download file