Kraloy PEJ150 is a 1-1/2-inch PVC expansion conduit fitting with 4 inches of travel to accommodate conduit length changes caused by temperature variation. Its telescoping two-tube design is pre-lubricated, includes O-rings to prevent leakage, and can be installed vertically or horizontally. Kraloy guidance calls for expansion joints when temperature changes exceed 25°F.
1-1/2-Inch PVC Fitting
4-Inch Travel
Thermal Length-Change Compensation
Telescoping Two-Tube Design
O-Rings Included
Vertical or Horizontal Installation
Kraloy PEJ150 is a 1-1/2-inch PVC expansion conduit fitting with 4 inches of travel to accommodate conduit length changes caused by temperature variation. Its telescoping two-tube design is pre-lubricated, includes O-rings to prevent leakage, and can be installed vertically or horizontally. Kraloy guidance calls for expansion joints when temperature changes exceed 25°F.
Kraloy PEJ150 is a 1-1/2-inch PVC expansion conduit fitting with 4 inches of travel to accommodate conduit length changes caused by temperature variation. Its telescoping two-tube design is pre-lubricated, includes O-rings to prevent leakage, and can be installed vertically or horizontally. Kraloy guidance calls for expansion joints when temperature changes exceed 25°F.
1-1/2-Inch PVC Fitting
4-Inch Travel
Thermal Length-Change Compensation
Telescoping Two-Tube Design
O-Rings Included
Vertical or Horizontal Installation
Technical Specifications
Product information and specifications for the selected item.
SKU: PEJ150
Product Information
Brand
Kraloy
SKU
PEJ150
Category
Conduit Fittings
Technical Details
Fitting Type
Coupling
Conduit Compatibility
PVC
Trade Size (in.)
1-1/2 in
Material
PVC
Height (in.)
2.23
Width (in.)
2.23
Length (in.)
13
Weight (lb.)
0.9
Sealing
Leakage protection
O-rings are included to prevent leakage.
Compliance
Certification markings
CSA and UL marks shown on the drawing
Certification marks
CSA and UL certification marks are shown on the expansion-joint specification sheet.
Installation
Piston alignment
Misalignment can cause the piston to bind.
Strap placement
Place straps approximately one foot on either side of the joint
Vertical mounting detail
For vertical installation, mount the piston downward to limit dirt accumulation between the barrel and piston.
Vertical orientation
Mount the piston downward in vertical installations to prevent dirt buildup at the muzzle
Support arrangement
Clamp the barrel tight while leaving the conduit loose enough in its hangers to move
Piston setting
Determine the piston setting based on installation temperature to allow for both expansion and contraction
Mounting orientation
Can be installed vertically or horizontally.
Alignment
Keep piston travel straight in the barrel to prevent binding
Construction
Construction
Two-tube construction, with one tube telescoping inside the other.
Lubrication
Pre-lubricated for smooth adjustment.
Seal components
O-rings
Sliding construction
Two tubes, one telescoping inside the other
Mechanical
Travel
4 in
Application
Thermal movement function
Compensates for conduit length changes caused by temperature variations.
Operating Conditions
Temperature-change threshold
Expansion joints are required when temperature change exceeds 25°F (14°C).
Application threshold
Use an expansion joint when expected temperature variation exceeds 25 °F