Kraloy PLR100 is a 1-inch PVC Type LR access fitting with two hubs and a 13.1 cu. in. fill volume. It provides a right-side 90° access, pull, or splice point and comes factory assembled with a PVC gasket, cover, threaded brass inserts, and brass screws. Join it to PVC conduit with Kraloy Solvent Cement.
1-Inch PVC Type LR Fitting
Right-Side 90° Access Turn
Two Hubs
13.1 cu. in. Fill Volume
Factory-Assembled with Included Parts
UL Listed for Wet Locations
Kraloy PLR100 is a 1-inch PVC Type LR access fitting with two hubs and a 13.1 cu. in. fill volume. It provides a right-side 90° access, pull, or splice point and comes factory assembled with a PVC gasket, cover, threaded brass inserts, and brass screws. Join it to PVC conduit with Kraloy Solvent Cement.
Kraloy PLR100 is a 1-inch PVC Type LR access fitting with two hubs and a 13.1 cu. in. fill volume. It provides a right-side 90° access, pull, or splice point and comes factory assembled with a PVC gasket, cover, threaded brass inserts, and brass screws. Join it to PVC conduit with Kraloy Solvent Cement.
1-Inch PVC Type LR Fitting
Right-Side 90° Access Turn
Two Hubs
13.1 cu. in. Fill Volume
Factory-Assembled with Included Parts
UL Listed for Wet Locations
Technical Specifications
Product information and specifications for the selected item.
SKU: PLR100
Product Information
Brand
Kraloy
SKU
PLR100
Category
Conduit Fittings
Technical Details
Fitting Type
Type LR Conduit Body
Conduit Compatibility
PVC
Trade Size (in.)
1 in
Material
PVC
Height (in.)
2
Width (in.)
1.75
Length (in.)
6.125
Weight (lb.)
0.3332
Capacity
Fill volume
13.1 cu in
Construction
Included components
Threaded brass inserts, brass screws, PVC gasket and cover
Cover hardware
Threaded brass screws and inserts
Assembly
Fully factory assembled
Impact characteristic
High impact
Cover durability
Can be removed as often as needed without wear or cracking
Hub count
2
Sealing
Gasket flexibility
Flexible
Installation
Joining method
Join with PVC conduit using Kraloy Solvent Cement
Conductor-pulling guidance
Pulling compound required for #4 AWG
Serviceability
Cover serviceability
Cover can be removed as often as needed without wear or cracking
Compliance
Wet-location listing
UL listed for wet locations
Applicable standards
UL 514C; CSA C22.2 No. 85
Environmental Resistance
Chemical resistance
Resistant to acids, alkalis or salt solutions
Corrosion resistance
Resistant to external corrosion and pitting; will not rust
Electrical
Electrical property
Nonconductive
Operating Conditions
NEC ambient-temperature use condition
Not in excess of 122 °F
Application
Conduit-run function
Access/pull/splice point with a 90° turn through the right side