The Kraloy PEJ200 is a 2-inch PVC expansion conduit fitting with 4 inches of travel for temperature-related length changes in exposed conduit runs. It uses a pre-lubricated telescoping mechanism and includes O-rings to help prevent leakage.
2-Inch PVC Expansion Fitting
4-Inch Expansion Travel
25°F Temperature-Change Threshold
Telescoping Two-Tube Design
Included O-Rings
CSA and UL Compliance
The Kraloy PEJ200 is a 2-inch PVC expansion conduit fitting with 4 inches of travel for temperature-related length changes in exposed conduit runs. It uses a pre-lubricated telescoping mechanism and includes O-rings to help prevent leakage.
The Kraloy PEJ200 is a 2-inch PVC expansion conduit fitting with 4 inches of travel for temperature-related length changes in exposed conduit runs. It uses a pre-lubricated telescoping mechanism and includes O-rings to help prevent leakage.
2-Inch PVC Expansion Fitting
4-Inch Expansion Travel
25°F Temperature-Change Threshold
Telescoping Two-Tube Design
Included O-Rings
CSA and UL Compliance
Technical Specifications
Product information and specifications for the selected item.
SKU: PEJ200
Product Information
Brand
Kraloy
SKU
PEJ200
Category
Conduit Fittings
Technical Details
Conduit Compatibility
PVC
Trade Size (in.)
2 in
Material
PVC
Height (in.)
2.85
Width (in.)
2.85
Length (in.)
9.25
Weight (lb.)
1.2999
Sealing
Seal
O-rings included to help prevent leakage
Compliance
Compliance standards/listing
CSA C22.2 No. 85; UL Listed
Compliance marks
CSA and UL (ULI) marks shown
Installation
Support-strap placement
Place straps approximately 1 ft on either side of the joint.
Barrel and conduit support
Clamp the barrel tightly while leaving the conduit loose enough in its hangers to move as it expands and contracts.
Piston alignment
Mount so the piston travels straight in the barrel; misalignment can cause binding and prevent correct operation.
Mounting orientation
Can be installed vertically or horizontally
Vertical orientation
When mounted vertically, position the piston downward to keep dirt from collecting at the muzzle.
Mounting and support
Clamp the barrel tight and leave the conduit loose enough in its hangers to move during expansion and contraction.
Operating Conditions
Application and temperature-change threshold
Designed to compensate for temperature-related length changes in exposed conduit runs; expansion joints are required when the temperature change exceeds 25°F (14°C).
Temperature-variation use condition
Expansion joints must be used where expected temperature variation exceeds 25°F.