The Littelfuse POWR-GARD KLKD30 is a 30 A fast-acting midget cartridge fuse rated for 600 V AC and 600 V DC. It has ferrule ends, is non-indicating, and is specified at 10 × 38 mm. Its stated role is supplementary backup overcurrent protection for a primary branch-circuit fuse or breaker.
30 A Current Rating
600 V AC/DC Rating
Fast-Acting Fuse
Midget 10 × 38 mm Format
Ferrule Ends
Non-Indicating Design
The Littelfuse POWR-GARD KLKD30 is a 30 A fast-acting midget cartridge fuse rated for 600 V AC and 600 V DC. It has ferrule ends, is non-indicating, and is specified at 10 × 38 mm. Its stated role is supplementary backup overcurrent protection for a primary branch-circuit fuse or breaker.
The Littelfuse POWR-GARD KLKD30 is a 30 A fast-acting midget cartridge fuse rated for 600 V AC and 600 V DC. It has ferrule ends, is non-indicating, and is specified at 10 × 38 mm. Its stated role is supplementary backup overcurrent protection for a primary branch-circuit fuse or breaker.
30 A Current Rating
600 V AC/DC Rating
Fast-Acting Fuse
Midget 10 × 38 mm Format
Ferrule Ends
Non-Indicating Design
Technical Specifications
Product information and specifications for the selected item.
SKU: KLKD30
Product Information
Brand
Littelfuse
MPN
KLKD30
SKU
KLKD30
Category
Fuses, Fuse Blocks & Holders
Key Specs
Current - Maximum
30 A
AC Voltage Rating
600 V AC
DC Voltage Rating
600 V DC
Fits Fuse Class or Type
Midget
Electrical Ratings
Current - Maximum
30 A
AC Voltage Rating
600 V AC
DC Voltage Rating
600 V DC
Average power loss at 80% rated current
1.983 W
AC interrupting rating
100 kA
Total clearing I²t at 20 kA, 600 V DC
2757 A²s
Opening time at 200% rated current (UL)
2 maximum min
Nominal cold resistance
0.002776 Ω
Apparent RMS symmetrical current for the 30 A fuse at 50 kA prospective short-circuit current
1556 A
Total melting I²t
1409 A²s
DC interrupting rating (UL 248-19)
10 kA
Total clearing I²t at 100 kA prospective AC fault, at rated voltage
3220 A²s
DC interrupting rating (UL 248-14)
50 kA
Opening time at 135% rated current (UL)
60 maximum min
Average melting I²t
1409 A²s
Total clearing I²t at 100 kA, 600 V AC
3220 A²s
Opening time at 105% rated current (IEC)
60 min
Total clearing I²t at 20 kA prospective DC fault, at rated voltage
2757 A²s
Power loss at 100% rated current
3.701 W
Fuse Type & Indication
Fits Fuse Class or Type
Midget
Visual Indication
Non-Indicating
Cap material
Copper alloy
EU RoHS directive
2011/65/EU
Applicable photovoltaic fuse standard
IEC 60269-6
EU Low Voltage Directive
2014/35/EU
Body material
Melamine
CSA certification
Certified; file LR29862
UL listing (US)
Files E339112 and E10480
Intended protection role
Supplementary backup overcurrent protection for a primary branch-circuit fuse or breaker
Dimensions & Weight
Height (in.)
0.406
Width (in.)
0.406
Length (in.)
1.5
Weight (lb.)
0.017
Product Documents
UL Certification — JFGA.E339112, Fuses for Photovoltaic Systems
Certification compliance
Open / download file
EU Declaration of Conformity — KLKD Series, including 30 A
Certification compliance
Open / download file