The Mersen Amp-Trap 2000 AJT40ID is a 40 A Class J time-delay fuse rated 600 V AC and 400 V DC. It has SmartSpot open-fuse indication and ferrule terminals, and accommodates typical motor and transformer inrush currents.
40 A Current Rating
600 VAC / 400 VDC Ratings
Class J Fuse Type
Time-Delay Operation
SmartSpot Open-Fuse Indication
Ferrule Terminals
The Mersen Amp-Trap 2000 AJT40ID is a 40 A Class J time-delay fuse rated 600 V AC and 400 V DC. It has SmartSpot open-fuse indication and ferrule terminals, and accommodates typical motor and transformer inrush currents.
The Mersen Amp-Trap 2000 AJT40ID is a 40 A Class J time-delay fuse rated 600 V AC and 400 V DC. It has SmartSpot open-fuse indication and ferrule terminals, and accommodates typical motor and transformer inrush currents.
40 A Current Rating
600 VAC / 400 VDC Ratings
Class J Fuse Type
Time-Delay Operation
SmartSpot Open-Fuse Indication
Ferrule Terminals
Technical Specifications
Product information and specifications for the selected item.
SKU: AJT40
Product Information
Brand
Mersen
MPN
AJT40
SKU
AJT40
Category
Fuses, Fuse Blocks & Holders
Key Specs
Current - Maximum
40 A
AC Voltage Rating
600 V AC
DC Voltage Rating
400 V DC
Fits Fuse Class or Type
Class J
Electrical Ratings
Current - Maximum
40 A
AC Voltage Rating
600 V AC
DC Voltage Rating
400 V DC
Interrupting rating
300 (self-certified; UL-witnessed tests) kA
Rated frequency
50/60 Hz
Self-certified interrupting rating
300 kA
DC interrupting rating
100 kA
AC interrupting rating
200 kA
Fuse Type & Indication
Fits Fuse Class or Type
Class J
Visual Indication
Indicating
Inrush handling
Typical motor and transformer inrush currents
Current-limiting characteristic
Extremely current limiting for low peak let-through current
Time-delay application
For motor starting and transformer inrush
Fuse end style
Ferrule
UK legislation compliance
Electrical Equipment (Safety) Regulations 2016 (S.I. 2016/1101); Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012 (S.I. 2012/3032)
UL listing
UL listed to standard 248-8, File E2137
CSA certification
CSA certified to standard C22.2 No. 248.8
Damage protection
IEC Type 2 No Damage protection for main, feeder, and branch circuits
Selectivity
2-to-1 selectivity to help prevent nuisance shutdowns
Current-limiting behavior
Low peak let-thru current
Applications
Motor circuits; mains; feeders; branch circuits; lighting, heating, and general loads; transformers; control panels; circuit breaker back-up; bus duct; load centers
Protection performance
IEC Type 2 No Damage protection for main, feeder, and branch circuits
DC listing
UL 248
IEC standard
IEC 60269-2-1
UK conformity standards
EN 60269-1: 2007/A1: 2009/A2: 2014; HD 60269-2: 2013
Dimensions & Weight
Height (in.)
1.062
Width (in.)
1.062
Length (in.)
2.37
Weight (lb.)
0.1669
Filler material
High-grade silica filler; fast arc quenching
Body material
Fiberglass body; dimensional stability in harsh environments