Skip to content
MGM Transformer Company

MGM Transformer Company 75kVA Three-Phase Dry-Type Transformer, 480V Delta to 240V Delta/120V Center Tap

0 Reviews
SKU
HT75A3K2-D16

The MGM Transformer Company HT75A3K2-D16 is a 75 kVA three-phase dry-type transformer with a 480 V delta primary and a 240 V delta/120 V center-tap secondary. It has aluminum windings and a 60 Hz operating frequency.

  • 75 kVA Rated Capacity
  • 480 V Delta Primary
  • 240 V Delta / 120 V Center-Tap Secondary
  • Three-Phase Dry-Type, 60 Hz
  • Aluminum Windings
  • UL and cUL Listings; CSA Certification

The MGM Transformer Company HT75A3K2-D16 is a 75 kVA three-phase dry-type transformer with a 480 V delta primary and a 240 V delta/120 V center-tap secondary. It has aluminum windings and a 60 Hz operating frequency.

Product Overview

The MGM Transformer Company HT75A3K2-D16 is a 75 kVA three-phase dry-type transformer with a 480 V delta primary and a 240 V delta/120 V center-tap secondary. It has aluminum windings and a 60 Hz operating frequency.

  • 75 kVA Rated Capacity
  • 480 V Delta Primary
  • 240 V Delta / 120 V Center-Tap Secondary
  • Three-Phase Dry-Type, 60 Hz
  • Aluminum Windings
  • UL and cUL Listings; CSA Certification

Technical Specifications

Product information and specifications for the selected item.

SKU: HT75A3K2-D16

Product Information

BrandMGM Transformer Company
MPNHT75A3K2-D16
SKUHT75A3K2-D16
CategoryElectrical Transformers

Key Specs

Rated Power (kVA)75
Temperature Rise (C)150
Winding MaterialAluminum

Capacity & Ratings

Rated Power (kVA)75
Temperature Rise (C)150
High-voltage tap configuration2A4B at 2-1/2%
Three-phase output terminalsConnect the three-phase output at X1, X2, and X3
Operating frequency60 Hz
Frequency60 Hz
Factory-default tap settingTap jumpers on positions 3–5 at nominal 480 V input
Single-phase output connectionsSingle-phase output connections are X1–X4 and X2–X4; each is 5% of capacity
Input-voltage limitDo not connect if utility voltage is higher than 504 V; contact MGM
High-voltage BIL10 kV
Low-voltage BIL10 kV
Insulation system rating220 °C
Tap-jumper alignmentSet all three coils’ tap jumpers to the same position
Incoming terminalsConnect utility three-phase supply to H1, H2, and H3
Single-phase loading effectUsing 10% single-phase output reduces three-phase capacity by 15%
Primary tap settingsTap pair 4–5: 504 V; 4–6: 492 V; 3–5: 480 V; 3–6: 468 V; 2–6: 456 V; 3–7: 444 V; 2–7: 432 V
Cooling classAA
Maximum warranted sound level50 dB

Construction

Winding MaterialAluminum
MaterialAluminum
Adjustment safetyAdjustments only by a qualified electrician; disconnect power before working on the transformer
Coil construction and impregnationContinuous-wound coils impregnated with nonhygroscopic, thermosetting varnish
Enclosure finishElectrostatically applied polymer polyester powder coating with a baking cycle
Mounting configurationBase mounted, rigid
Coating colorANSI 61
Enclosure ventilationVentilated enclosure
Core/coil vibration isolationCore and coil bolted to the enclosure base and isolated by rubber vibration-absorbing mounts
Core groundingCore visibly grounded to the enclosure by a flexible grounding conductor sized to applicable UL and NEC standards

Certifications

Certifications and ListingsCSA Certified, cUL Listed, DOE, UL Listed

Dimensions & Weight

Height (in.)38.5
Width (in.)28.5
Length (in.)20
Weight (lb.)574

Product Documents

  • Three Phase 480-240/120 CT Nameplate and Wiring Diagram Other Open / download file
  • HCAI Special Seismic Certification Preapproval OSP-0056 - MGM Dry-Type General Purpose and Unit Substation Transformers Certification compliance Open / download file
  • General Purpose Dry Type Transformer O&M Manual Installation manual Open / download file
  • 600V Class Dry-Type General Purpose Distribution Transformer Specification Guide Spec sheet Open / download file

Your cart

0 products 0 units

Your cart is empty.