Midwest Electric Products U035F2 is a 30 A fused pull-out air-conditioner disconnect for 120/240 V single-phase AC circuits. It carries a 3 HP rating and NEMA 3R enclosure rating, is cULus listed, and is specified for service-entrance use.

  • 30 A, 120/240 V Single-Phase
  • Fused Pull-Out Disconnect
  • NEMA 3R Enclosure
  • 3 HP Rating
  • 10 kA AIC
  • Compatible Fuse Classes

Product Overview

Midwest Electric Products U035F2 is a 30 A fused pull-out air-conditioner disconnect for 120/240 V single-phase AC circuits. It carries a 3 HP rating and NEMA 3R enclosure rating, is cULus listed, and is specified for service-entrance use.

Technical Specifications

Product information and specifications for the selected item.

SKU: U035F2

Product Information

BrandMidwest Electric Products
MPNU035F2
SKUU035F2
UPC / GTIN784567301021
CategoryDisconnects & Safety Switches

Key Specs

Maximum Amperage (A)30
Phase Type1 Phase
Disconnect TypeAir Conditioner
NEMA Enclosure RatingNEMA 3R

Switch Ratings

Maximum Amperage (A)30
Phase Type1 Phase
Maximum available fault current10,000 A RMS symmetrical at 240 V AC max
Rated voltage120/240 V AC
Voltage system120/240 VAC
Horsepower rating3 HP
Conductor size rangeLine/load: copper solid 14–8, stranded 14–2; aluminum solid 12–8, stranded 12–2. Equipment ground: copper and aluminum solid 12–8, stranded 12–2. AWG
DC ratingNot DC rated
AIC10,000
Single-wire lug torque40 for 14–10; 45 for 8 and 6–4; 50 for 3–2/0 in-lb
Motor fuse selection guidanceStarting current of motors above the standard horsepower ratings may require fuses with appropriate time-delay characteristics.
Terminal wire temperature ratings60 and 75 °C
Line/load conductor rangeCopper: 14-8 solid, 14-2 stranded; aluminum: 12-8 solid, 12-2 stranded AWG
Equipment grounding conductor rangeCopper and aluminum: 12-8 solid, 12-2 stranded AWG
Continuous-load conditionContinuous load in non-motor circuits must not exceed 80% of the fuse rating.

Disconnect Configuration

Disconnect TypeAir Conditioner
FusedFused
Compatible fuse classesClass H, K1, K5, K9, RK1, or RK5
Puller operationPullers are removable or reinstallable in the OFF position for maintenance safety.
Puller removal positionRemovable or reinstallable in the OFF position

Enclosure & Certifications

NEMA Enclosure RatingNEMA 3R
Certifications and ListingscULus Listed
ConstructionThree-piece construction opens mounting and wiring areas
Enclosure material and finishG90 galvanized steel with a durable polyester powder-coat finish; finish resists chipping and fading.
Service entrance applicationFor service entrance use.
Housing material and finishG90 zinc-coated galvanized steel with electro-deposition finish
Application restrictionsNot intended for EV charging, photovoltaic (PV), or non-resistive heating applications.
Service-entrance useListed for use as service entrance

Dimensions & Weight

Height (in.)7.4
Width (in.)5.1
Length (in.)2.8
Weight (lb.)2.5
Mounting holesThree 5/16-in. mounting holes.
Conduit knockoutsSix knockouts for 1/2, 3/4, and 1-in. sizes.