The Oracle Battery FS645 is a 6 V sealed lead-acid AGM battery rated at 4.5 Ah at the 20-hour rate, with F1 terminals and a specified 3–5-year standby service life at a consistent 25°C.
6 V Nominal Rating
4.5 Ah at 20-Hour Rate
F1 Terminals
Case Dimensions
Sealed VRLA AGM Design
3–5-Year Standby Service Life
The Oracle Battery FS645 is a 6 V sealed lead-acid AGM battery rated at 4.5 Ah at the 20-hour rate, with F1 terminals and a specified 3–5-year standby service life at a consistent 25°C.
The Oracle Battery FS645 is a 6 V sealed lead-acid AGM battery rated at 4.5 Ah at the 20-hour rate, with F1 terminals and a specified 3–5-year standby service life at a consistent 25°C.
6 V Nominal Rating
4.5 Ah at 20-Hour Rate
F1 Terminals
Case Dimensions
Sealed VRLA AGM Design
3–5-Year Standby Service Life
Technical Specifications
Product information and specifications for the selected item.
SKU: FS645
Product Information
Brand
Oracle Battery
MPN
FS645
SKU
FS645
Category
Emergency Lights & Exit Signs
Ratings & Use
Cycle-use charge voltage
7.2 to 7.5 V
Nominal capacity
4.5 at a 20-hour rate to 1.75 V per cell Ah
Container material
ABS
Battery technology
Valve-regulated lead-acid (VRLA), absorbent glass mat (AGM); safe to operate in any position
Transportation classification and compliance
Non-spillable; described as non-hazardous for normal transportation, approved for air transport, and stated to fulfill US D.O.T., I.A.T.A., F.A.A., and C.A.B. handling and shipping requirements
Discharge temperature range
-15°C (5°F) to 50°C (122°F)
Flame-retardant case/cover classification
UL94-HB
Cells per unit
3 cells
Standby charge voltage
6.75 to 6.90 V
Maximum discharge current (5 seconds)
60 A
Standby service life
3–5 years in normal standby applications at consistent 25°C
UL file number
MH61846
Operating position
Any position
Internal resistance at 1 kHz
45 mΩ
Charging temperature range
0°C (32°F) to 40°C (104°F)
UL recognition
UL recognized (UR) as a component in UL-approved equipment installations; File MH61846
Discharging ambient temperature range
-15 to 50 °C
Storage temperature range
-15°C (5°F) to 40°C (104°F)
Case construction and flammability rating
Externally sealed, flame-retardant ABS case and cover to UL94-HB specifications
Maximum charge current
0.8 A
Terminal type
F1
Grid and lead materials
Lead-calcium alloy grids with high-purity virgin lead
Recharge interval during storage
At 68°F: every 9 months; at 77°F: every 6 months; at 95°F: every 3 months