Skip to content
Park

Park PM 123-15 15kV 600A Pad-Mounted Primary Switch and Metering Cubicle

0 Reviews
SKU
PM123-15

Park PM123-15 is a 15 kV pad-mounted primary switch and metering cubicle with manually operated 600 A fused interrupter switches and S&C power fuses. Its S&C Mini-Rupter switches have a 17 kV maximum design voltage, 95 kV BIL, and a 40 kA asymmetrical momentary/fault-close rating. The unit has a NEMA 3R welded-steel enclosure, silver-plated copper bus, internal space heaters, and UL Listing.

  • 15 kV, 600 A Switchgear
  • 17 kV Design Voltage, 95 kV BIL
  • 40 kA Momentary/Fault-Close Rating
  • S&C Power Fuses
  • NEMA 3R Enclosure
  • UL Listed

Park PM123-15 is a 15 kV pad-mounted primary switch and metering cubicle with manually operated 600 A fused interrupter switches and S&C power fuses. Its S&C Mini-Rupter switches have a 17 kV maximum design voltage, 95 kV BIL, and a 40 kA asymmetrical momentary/fault-close rating. The unit has a NEMA 3R welded-steel enclosure, silver-plated copper bus, internal space heaters, and UL Listing.

Product Overview

Park PM123-15 is a 15 kV pad-mounted primary switch and metering cubicle with manually operated 600 A fused interrupter switches and S&C power fuses. Its S&C Mini-Rupter switches have a 17 kV maximum design voltage, 95 kV BIL, and a 40 kA asymmetrical momentary/fault-close rating. The unit has a NEMA 3R welded-steel enclosure, silver-plated copper bus, internal space heaters, and UL Listing.

  • 15 kV, 600 A Switchgear
  • 17 kV Design Voltage, 95 kV BIL
  • 40 kA Momentary/Fault-Close Rating
  • S&C Power Fuses
  • NEMA 3R Enclosure
  • UL Listed

Technical Specifications

Product information and specifications for the selected item.

SKU: PM123-15

Product Information

BrandPark
MPNPM123-15
SKUPM123-15
CategoryDisconnects & Safety Switches

Key Specs

Maximum Amperage (A)600
NEMA Enclosure RatingNEMA 3R

Switch Ratings

Maximum Amperage (A)600
S&C Mini-Rupter magnetizing interrupting current21 A RMS
Bus connection material and finishCopper bus with silver plating
S&C Mini-Rupter basic impulse level (BIL)95 kV
S&C Mini-Rupter momentary and fault-close rating (asymmetrical)40 kA asym
S&C Mini-Rupter maximum design voltage17 kV
S&C Mini-Rupter capacitive interrupting current36 A RMS

Disconnect Configuration

FusedFused
Switch handle typeRemovable
Interrupter switch maintenanceMaintenance-free

Enclosure & Certifications

NEMA Enclosure RatingNEMA 3R
Certifications and ListingsUL Listed
Ventilation-louver weather and corrosion resistanceCorrosionproof and rainproof
Door hold-open holder operationFoot-operated
Enclosure constructionSteel enclosure built by welding
HV meter-bay design basisBuilt to utility specifications
Interior heater provisionSpace heaters inside each unit
Door hinge pivot materialBrass pivots
Door latch securityLockable

Dimensions & Weight

Height (in.)82
Width (in.)40
Length (in.)60
Required right-side clearance for handle operation7 ft
Required front and rear clearance4 ft
Channel-base size3 in.