The PQ Protection PQCF320-S is a panel-mounted surge protective device for 120/208 V, 3-phase Wye, 4-wire-plus-ground systems. It is rated 320 kA per phase (160 kA per mode) and includes an EMI filter and surge counter.

  • 120/208 V 3-Phase Wye
  • 320 kA Per Phase, 160 kA Per Mode
  • Panel Mount, 3/4-Inch Nipple
  • 200 kA Short-Circuit Rating
  • UL Type 2
  • NEMA 4X Enclosure

Product Overview

The PQ Protection PQCF320-S is a panel-mounted surge protective device for 120/208 V, 3-phase Wye, 4-wire-plus-ground systems. It is rated 320 kA per phase (160 kA per mode) and includes an EMI filter and surge counter.

Technical Specifications

Product information and specifications for the selected item.

SKU: PQCF320-S-120/208V-3Y

Product Information

BrandPQ Protection
MPNPQCF320-S-120/208V-3Y
SKUPQCF320-S-120/208V-3Y
CategorySurge Protective Devices

Key Specs

Surge Current Capacity (kA)320
Connection typePanel Mount

Surge Ratings

Surge Current Capacity (kA)320
Maximum Continuous Operating Voltage (MCOV)150/300 V
Maximum ambient temperature+85 °C
Ground-reference indication thresholdIndicates when neutral-to-ground potential exceeds approximately 20 V
Operating frequency50, 60, 400 Hz
Nominal Discharge Current (In)20 kA
Relative humidity0% to 95% (noncondensing)
Audible alarm behaviorSounds upon suppression-element failure; may be silenced by removing power to the SPD.
EMI filter attenuation−39.7 at 100 kHz dB
Short Circuit Current Rating (SCCR)200 kA
Surge counterStandard on PQCF320-S EMI filter models
LED operationTwo green LEDs per line; green indicates complete protection, and the failed-mode LED extinguishes upon MOV failure.
Reset behaviorAutomatically resets after activation
Internal overload protectionInternal overload protection elements are included.
Voltage Protection Rating (VPR) by modeL-G: 700; L-N: 600; N-G: 600; L-L: 1000 V

Connection & Certifications

Connection typePanel Mount
Certifications and ListingsANSI Compliant, ISO 9001, UL Listed
Mounting method3/4-inch nipple mount
Lead placement guidanceInstall close to the circuit and use the shortest, straightest possible leads to minimize let-through voltage.
Grounding requirementAn equipment grounding conductor is required on all connected electrical circuits.
Remote monitoring contact type and ratingForm C monitoring contacts; 2 A at 240 V
Installation locationLoad side of the service overcurrent device only
System configuration120/208 V, 3-phase Wye, 4W+G
Enclosure ratingNEMA 4X
Remote contact behaviorContacts change state during inoperative conditions, including loss of power.
Recommended circuit breaker30 recommended; 20 minimum; multi-pole as required

Dimensions & Weight

Height (in.)6.9
Width (in.)6.9
Length (in.)3
Weight (lb.)4
Enclosure materialPolycarbonate

Product Documents