Skip to content
KOHLER

RDT 200A Service-Entrance Automatic Transfer Switch

0 Reviews
SKU
RDT-CFNC-200ASEQS4

KOHLER's RDT-CFNC-200ASEQS4 is a 200 A automatic service-entrance transfer switch specified for 240 V, single-phase, 2-pole, 3-wire operation. It uses an MPAC 500 controller and has an aluminum, water-resistant enclosure specified for indoor or outdoor use. This model is specified without a load center.

  • 200 A Maximum Rating
  • 240 V, Single-Phase, 2-Pole, 3-Wire
  • Service-Entrance WCR
  • MPAC 500 Controller
  • Aluminum Indoor/Outdoor Enclosure
  • UL Listed; ANSI Compliant

Product Overview

KOHLER's RDT-CFNC-200ASEQS4 is a 200 A automatic service-entrance transfer switch specified for 240 V, single-phase, 2-pole, 3-wire operation. It uses an MPAC 500 controller and has an aluminum, water-resistant enclosure specified for indoor or outdoor use. This model is specified without a load center.

Technical Specifications

Product information and specifications for the selected item.

SKU: RDT-CFNC-200ASEQS4

Product Information

BrandKOHLER
MPNRDT-CFNC-200ASEQS4
SKURDT-CFNC-200ASEQS4
UPC / GTIN650531408082
CategoryAutomatic Transfer Switches

Key Specs

Maximum Amperage (A)200
Automatic/ManualAutomatic
Certifications and ListingsANSI Compliant, UL Listed

Electrical Ratings

Maximum Amperage (A)200
PhaseSingle phase
Engine-start contact rating1 at 30 VDC; SPST normally closed (NC)
Load-control contact rating10 at 120 VAC; SPST normally open (NO)
Load wire range(1) #6 AWG–250 KCMIL Cu/Al conductor per phase
Common-fault contact rating0.5 at 125 VAC; 2 at 30 VDC; SPST normally open (NO)
Neutral wire range(5) #12–250 KCMIL Cu or (5) #10–250 KCMIL Al Conductors
External power terminalsAL/CU UL-listed solderless screw-type terminals
Service-entrance withstand and close-on rating (WCR)22,000 RMS symmetrical at 240 VAC
Emergency-source wire range(1) #6–250 KCMIL Cu/Al conductor per phase
Normal-source wire range(1) #4–300 KCMIL Cu/Al conductor per phase

Transfer & Features

Automatic/ManualAutomatic
FeaturesOn Indicator Light, Water Resistant
Engine cooldown delay5 factory; adjustable 1–10 in 1-minute increments with accessory board minutes
Normal-to-emergency transfer delay3 factory; adjustable 1–10 in 1-second increments with accessory board seconds
Undervoltage dropout delay0.5; not adjustable seconds
Emergency-to-normal retransfer delay6 factory; adjustable 3–30 in 3-minute increments with accessory board minutes
Underfrequency dropout threshold90 %
Operating temperature−20 to 70 °C
Underfrequency dropout delay3; not adjustable seconds
Storage temperature−40 to 85 °C
Emergency-source acquisition failure delay78; not adjustable seconds
Engine-start delay3 factory; adjustable 1–10 in 1-second increments with accessory board seconds
Humidity range5 to 95, noncondensing %
Undervoltage pickup threshold85 %
Undervoltage dropout threshold80 %
Underfrequency pickup threshold96 %

Certifications

Certifications and ListingsANSI Compliant, UL Listed

Dimensions & Weight

Height (in.)33.8
Width (in.)18.6
Length (in.)6.4
Weight (lb.)26

Product Documents

  • Model RDT and RXT Transfer Switches — Five-Year Limited Warranty, United States (TP-7231, 1/24b) Warranty Open / download file
  • Model RDT Automatic Transfer Switch, 100–400 Amps — Specification Sheet (G11-151) Spec sheet Open / download file