Skip to content
Roof Top Blox

Roof Top Blox RTB-01 Adjustable Rooftop Piping Support Block

0 Reviews
SKU
RTB-01

Roof Top Blox RTB-01 is an adjustable rooftop support block specified for 2-in. pipe and flat-roof support of electrical conduit. It combines a UV-stabilized polypropylene body, a 1-in. closed-cell foam base, and molded pipe saddles with a strut cradle. It is designed for rooftop installation without roof penetrations or flashings.

  • Adjustable 2-in. pipe support
  • 250/350 lb per-block load ratings
  • UV-stabilized polypropylene body
  • 1-in. closed-cell foam base
  • Molded pipe saddles and strut cradle
  • 8-7/8-in. square footprint

Roof Top Blox RTB-01 is an adjustable rooftop support block specified for 2-in. pipe and flat-roof support of electrical conduit. It combines a UV-stabilized polypropylene body, a 1-in. closed-cell foam base, and molded pipe saddles with a strut cradle. It is designed for rooftop installation without roof penetrations or flashings.

Product Overview

Roof Top Blox RTB-01 is an adjustable rooftop support block specified for 2-in. pipe and flat-roof support of electrical conduit. It combines a UV-stabilized polypropylene body, a 1-in. closed-cell foam base, and molded pipe saddles with a strut cradle. It is designed for rooftop installation without roof penetrations or flashings.

  • Adjustable 2-in. pipe support
  • 250/350 lb per-block load ratings
  • UV-stabilized polypropylene body
  • 1-in. closed-cell foam base
  • Molded pipe saddles and strut cradle
  • 8-7/8-in. square footprint

Technical Specifications

Product information and specifications for the selected item.

SKU: RTB-01

Product Information

BrandRoof Top Blox
MPNRTB-01
SKURTB-01
CategoryHangers & Supports

Key Specs

Pipe Hangers & Supports TypePipe Hanging Mount
Pipe/Rod Size (in.)2 in
Length (in.)8.875
Width (in.)8.875

Support & Fit

Pipe Hangers & Supports TypePipe Hanging Mount
Pipe/Rod Size (in.)2 in
Base and roof-contact constructionType 4 closed-cell structural foam, 25 psi; no rigid plastic or sharp corners contact the roof membrane.
Permanent roof securementAfter system installation, permanently secure each Blox with SCB-07 brackets and ADH-12 adhesive.
Maximum load by configurationSingle-point: 250 lb (113 kg); dual-point or strut-mounted: 350 lb (158 kg).
Fastener torqueMaximum 15 ft-lb on Blox-top jamb nuts; apply threadlocker to threads.
Maximum dual-point or strut-mounted load per block350 lb
Recommended fastening screws#10 sheet-metal screws are recommended.
Cold-temperature drop testPassed three 48-in drops at 0°F onto structural concrete, with no visible cracking, fracture, plastic deformation, or foam-base disengagement.
Load positioningPlace loads as low as possible and center them on the Blox for stability.
Maximum rated temperatureUp to 200°F (93°C).
Strut requirement for heavy loadsInstall STR-04 slotted strut beneath loads over 250 lb (113 kg) per Blox.
Hardware coatingUse only zinc- or galvanized-coated steel hardware.
Mounting interfaceMolded-in pipe saddles and strut cradle; screw-guide indents and internal thread grip; accepts clamps, clips, or slotted strut, with fastening and adjustments from the top side only.
Load rating conditionsLoad ratings apply to static conditions; dynamic and seismic loads are not included.
Placement spacingSpace approximately every 7 ft along piping on flat or low-pitch rooftops.
Wind test resultWith SCB-07 brackets and ADH-12 adhesive, test specimens passed 150-mph fan exposure for 1 hour on each principal face, with no movement or detachment from the substrate.
High-temperature load testPassed an 8-hour test at 200°F with a 350 lb distributed strut load.
Roof installation designDesigned for installation without roof penetrations or flashings, avoiding roofing-membrane damage.
Water absorption testAfter 24 hours submerged, RTB-01 showed insignificant water absorption.
Wind test scopeThe wind-tunnel test did not include mounted piping and is not a seismic test.
Maximum single-point load per block250 lb
Multi-block configurationBlocks can link end-to-end into continuous platforms or form 2- or 4-block bridge assemblies using galvanized strut.
Supported rooftop servicesSpecified for flat-roof support of gas, condensate or refrigeration lines, electrical conduits, ductwork, rooftop walkways, and mechanical equipment.
Body fabricationInjection-molded high-impact polypropylene copolymer resin fortified with UV inhibitors.

Dimensions & Weight

Height (in.)4.5
Width (in.)8.875
Length (in.)8.875
Weight (lb.)1
Body material and wall thicknessBlack UV-stabilized polypropylene copolymer; wall thickness 0.100–0.135 in