Schneider Electric Easy Harmony XB2 1 NO Spring-Return Contact Block, Front-Mount, Screw-Clamp Terminals
0 Reviews
SKU
ZB2BE101C
Schneider Electric Easy Harmony XB2 contact block ZB2BE101C provides one normally open contact for single-speed spring-return operators. It is front-mount, uses screw-clamp terminals, and has a 10 A conventional thermal current and 600 V rated insulation voltage.
Single NO Contact
Spring-Return Operator Use
Front-Mount Configuration
Screw-Clamp Terminals
10 A Conventional Thermal Current
600 V Rated Insulation
Schneider Electric Easy Harmony XB2 contact block ZB2BE101C provides one normally open contact for single-speed spring-return operators. It is front-mount, uses screw-clamp terminals, and has a 10 A conventional thermal current and 600 V rated insulation voltage.
Schneider Electric Easy Harmony XB2 contact block ZB2BE101C provides one normally open contact for single-speed spring-return operators. It is front-mount, uses screw-clamp terminals, and has a 10 A conventional thermal current and 600 V rated insulation voltage.
Single NO Contact
Spring-Return Operator Use
Front-Mount Configuration
Screw-Clamp Terminals
10 A Conventional Thermal Current
600 V Rated Insulation
Technical Specifications
Product information and specifications for the selected item.
SKU: ZB2BE101C
Product Information
Brand
Schneider Electric
MPN
ZB2BE101C
SKU
ZB2BE101C
UPC / GTIN
3606480975844
Category
Device Accessories
Accessory & Compatibility
Contact material
Silver alloy (Ag/Ni)
Rated impulse withstand voltage
6 kV
Conventional thermal current
10 enclosed; 10 free-air
Short-circuit protection
10 A cartridge fuse protection, type gG (gl)
Electrical shock protection class
Class II
Positive opening
Without
Terminal conductor capacity
1 × 2.5 or 2 × 1.5, with or without cable ends mm²
Utilization category ratings
A600 AC-15: 3 A at 240 V and 1.2 A at 600 V; Q600 DC-13: 0.27 A at 250 V and 0.1 A at 600 V
Electrical reliability
Λ < 10exp(-6) at 5 V, 1 mA; Λ < 10exp(-8) at 17 V, 5 mA in a clean environment
Contact operation
Slow-break
Product certifications
CE; CCC
Shock resistance
30 gn at 18 ms and 50 gn at 11 ms (half-sine wave acceleration)
Rated operational power
40 W at 120 V; 48 W at 48 V; 65 W at 24 V, DC-13 (each for 1,000,000 cycles, <3600 cycles/h, load factor 0.5)
Terminal tightening torque
0.8–1.0 N·m
Storage ambient temperature
-40…70 °C
Operating force
3–5 N
Mechanical durability
3,000,000 cycles
Rated insulation voltage
600 (pollution degree 3) V
Vibration resistance
5 gn at 2…500 Hz
Electrical durability
1,000,000 cycles at AC-15, 3 A/240 V; 1,000,000 cycles at DC-13, 0.27 A/250 V (each <3600 cycles/h, load factor 0.5)