Skip to content
Schneider Electric

Schneider Electric TeSys Deca LRD22 Thermal Overload Relay, 16–24A, Class 10A

0 Reviews
SKU
LRD22

Schneider Electric's TeSys Deca LRD22 is a thermal overload relay for motor protection, with an adjustable 16–24 A range and Class 10A trip class. It is specified for 690 V AC, DIN-rail mounting, and use with TeSys D contactors.

  • Adjustable 16–24 A Range
  • Class 10A Trip Class
  • 690 V AC Rating
  • DIN-Rail Mounting
  • TeSys D Contactor Compatibility
  • 1 NO + 1 NC Auxiliary Contacts

Schneider Electric's TeSys Deca LRD22 is a thermal overload relay for motor protection, with an adjustable 16–24 A range and Class 10A trip class. It is specified for 690 V AC, DIN-rail mounting, and use with TeSys D contactors.

Product Overview

Schneider Electric's TeSys Deca LRD22 is a thermal overload relay for motor protection, with an adjustable 16–24 A range and Class 10A trip class. It is specified for 690 V AC, DIN-rail mounting, and use with TeSys D contactors.

  • Adjustable 16–24 A Range
  • Class 10A Trip Class
  • 690 V AC Rating
  • DIN-Rail Mounting
  • TeSys D Contactor Compatibility
  • 1 NO + 1 NC Auxiliary Contacts

Technical Specifications

Product information and specifications for the selected item.

SKU: LRD22

Product Information

BrandSchneider Electric
MPNLRD22
SKULRD22
UPC / GTIN3389110346848
CategoryCircuit Breakers

Key Specs

Maximum Amperage (A)24
Voltage690 V AC
Mounting TypeDin Rail

Electrical Ratings

Maximum Amperage (A)24
Voltage690 V AC
Network frequency0 to 400 Hz
Tripping threshold1.14 +/- 0.06 Ir (IEC 60947-4-1)
Supported network typesAC and DC
Operating ambient temperature-20 to 60 °C without derating
Associated fuse rating4 A gG or 4 A BS for the signalling circuit
Conventional free-air thermal current5 A for the signalling circuit
Phase-failure sensitivityTrip current is 130% of Ir on two phases; the last phase is at 0.
Storage temperature-60 to 70 °C

Breaker Configuration

Mounting TypeDin Rail
Series TypeTeSys Deca
Relay applicationMotor protection
ControlsRed push-button stop; blue push-button reset
Compatible productsLC1D25, LC1D32, LC1D38
Restart after overload tripAfter a motor-overload trip, do not restart until the motor has cooled completely.
Power-circuit terminalsScrew-clamp terminals; 1 conductor; 1.5–10 mm² flexible without cable end or solid; 1–6 mm² flexible with cable end
Auxiliary contact composition1 NO + 1 NC
Configuration requirementFor explosive-atmosphere applications, qualified, trained service personnel must configure the relay and adapt its thermal class and motor current to the protected motor.
Terminal tightening torqueControl circuit: 1.7 N·m; power circuit: 2.5 N·m
Control-circuit terminalsScrew-clamp terminals; 2 conductors; 1–2.5 mm² flexible (with or without cable end) or solid

Pack & Smart Features

Bundle/SingleSingle Product
Pack OptionsSingle Item

Certifications

Certifications and ListingsCSA Certified, ROHS, UL Certified
REACH SVHC contentNo SVHC above the 0.1% threshold at part level
Hazardous-area installation and useInstall outside Ex zones; intended to protect explosion-protected motors in Zones 1–2 or 21–22.
Flame retardanceV1 (UL 94)
Ingress protectionIP20
California Proposition 65 warningCalifornia Proposition 65 warning: may expose users to antimony oxide and antimony trioxide, identified as known to the State of California to cause cancer.
REACH Annex XVII substancesNo Annex XVII restricted substance is used within the scope of restriction.

Dimensions & Weight

Height (in.)2.6
Width (in.)1.77
Length (in.)2.76
Weight (lb.)0.273
Vibration and shock resistanceVibration: 6 Gn; shock: 15 Gn for 11 ms

Product Documents

Your cart

0 products 0 units

Your cart is empty.

Add products as you browse, then review them here.